User-Programmable Self-Tests - GE G60 Instruction Manual

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
The user-programmable LED settings select the FlexLogic operands that control the LEDs. If the
Reset" (the default setting), the LED illumination tracks the state of the selected LED operand. If the
"Latched," the LED, once lit, remains so until reset by the faceplate
communications channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5-15: Recommended settings for user-programmable LEDs
Setting
Parameter
LED 1 operand
SETTING GROUP ACT 1
LED 2 operand
SETTING GROUP ACT 2
LED 3 operand
SETTING GROUP ACT 3
LED 4 operand
SETTING GROUP ACT 4
LED 5 operand
SETTING GROUP ACT 5
LED 6 operand
SETTING GROUP ACT 6
LED 7 operand
Off
LED 8 operand
Off
LED 9 operand
Off
LED 10 operand
Off
LED 11 operand
Off
LED 12 operand
Off
See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of group
activation.

5.3.12 User-programmable self-tests

SETTINGS  PRODUCT SETUP  USER-PROGRAMMALBE SELF TESTS
 USER-PROGRAMMABLE
 SELF TESTS
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Setting
LED 13 operand
LED 14 operand
LED 15 operand
LED 16 operand
LED 17 operand
LED 18 operand
LED 19 operand
LED 20 operand
LED 21 operand
LED 22 operand
LED 23 operand
LED 24 operand
DIRECT RING BREAK
FUNCTION: Enabled
DIRECT DEVICE OFF
FUNCTION: Enabled
RxGOOSE OFF
FUNCTION: Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
SFP MODULE FAIL
FUNCTION: Disabled
BATTERY FAIL
FUNCTION: Enabled
SNTP FAIL
FUNCTION: Enabled
IRIG-B FAIL
FUNCTION: Enabled
PTP FAIL
FUNCTION: Enabled
button, from a remote device via a
RESET
Parameter
Off
Off
Off
Off
SYNC 1 SYNC OP
SYNC 2 SYNC OP
Off
Off
Off
Off
Off
Off
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
PRODUCT SETUP
setting is "Self-
LED 1 TYPE
setting is
LED 1 TYPE
5-109
5