CHAPTER 5: SETTINGS
5.8.12.7 Thermal overload protection (ANSI 49)
SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  THERMAL OVERLOAD PROTECTION 
THERMAL PROTECTION 1(2)
 THERMAL
 PROTECTION 1
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-196: VT fuse fail logic
THERMAL PROTECTION 1
FUNCTION: Disabled
THERMAL PROTECTION 1
SOURCE: SRC1
THERMAL PROTECTION 1
BASE CURR: 0.80 pu
THERMAL PROTECTION 1
k FACTOR: 1.10
THERM PROT 1 TRIP
TIME CONST: 45 min
THERM PROT 1 RESET
TIME CONST: 45 min
THERM PROT 1 MINIM
RESET TIME: 20 min
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0.20 to 3.00 pu in steps of 0.01
Range: 1.00 to 1.20 in steps of 0.05
Range: 0 to 1000 min. in steps of 1
Range: 0 to 1000 min. in steps of 1
Range: 0 to 1000 min. in steps of 1