GE G60 Instruction Manual page 342

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

SYSTEM SETUP
— The SV Stream Control is set by either toggling an assigned FlexLogic operand or a remote client write, to
R-SV CB1 SVENA
start and stop the streaming of R-SV frames. If remote client control is disabled, a negative response is provided to the
client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that reflects the state of
the SvEna control where "1"= Enabled and "0"=Disabled. The figure shows the logic for setting the SvEna control bit.
5
R-SV CB1 CLIENT CONTRL
operand is a logic 1 state, remote clients can write to both the reserve bit and the SvEna bit. When the FlexLogic operand
is a logic 0 state, the remote client writes to the reserve bit, the SvEna is rejected by the UR, and a negative response with
the appropriate Service Error is returned to the client.
R-SV CB1 SVENA DFLT
R-SV CB1 CONFREV
allows the user to reset the configuration back to 1 or a value from 1 to 4294967295.
R-SV CB1 PRIORITY
R-SV CB1 DSCP CLASS
default value is set for Expedited Forwarding (101110B (46 or 2EH). This value provides priority routing, when supported in
the routers.
— A range of values limited from 0 to 4095.
R-SV CB1 VLAN ID
— This setting allows the selection of a specific application ID for each sending device.
R-SV CB1 APPID
5-166
R-SV CB1 PRIORITY:
4
R-SV CB1 CSCP CLASS:
Expedited Forwarding
R-SV CB1 VLAN ID:
0
R-SV CB1 APPID:
0
R-SV CB1 DEST IP:
224.0.0.0
R-SV CB1 SECURITY:
0
Figure 5-85: Logic for setting SvEna control bit
— This setting determines if a client can write to the reserve bit. When the assigned FlexLogic
— This setting sets the default state of the stream (On or Off) on power-up or restart.
— The relay increments the Configuration revision every time the configuration is changed. This setting
— A value from 0 through 7. The default value is 4.
— The value represents the IPv4 Differentiated Services (formerly called TypeOfService) value. The
Range: 0 to 7
Range: None, Expedited Forwarding
Range: 0 to 4095
Range: 0 to 16383
Range: 0 to 255.255.255.255
Range: 0 to 2
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL