TARGETS MENU
FLEXLOGIC ERROR:
with 2nd line detail
Latched target message: No.
Description of problem: A FlexLogic equation is incorrect.
How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified
What to do: Finish all equation editing and use self tests to debug any errors.
UNIT NOT PROGRAMMED:
Check Settings
Latched target message: No.
Description of problem: The
programmed.
How often the test is performed: On power up and whenever the
setting is altered
What to do: Program all settings and then set
MODULE FAILURE___:
Contact Factory (xxx)
Latched target message: Yes.
Description of problem: Module hardware failure detected. Module Failures 1 to 11 are major. The system can reboot
for four of these, as follows.
MODULE FAILURE 06 — Event message reads SYSTEM INTEGRITRY RECOVERY 06 when a reboot was required and
otherwise MODULE FAILURE 06 when a failure was detected
MODULE FAILURE 07 — Event message reads SYSTEM INTEGRITRY RECOVERY 07 when a reboot was required and
otherwise MODULE FAILURE 07 when a failure was detected
MODULE FAILURE 08 — Event message reads SYSTEM INTEGRITRY RECOVERY 08 when a reboot was required and
otherwise MODULE FAILURE 08 when a failure was detected
MODULE FAILURE 11 — Event message reads SYSTEM INTEGRITRY RECOVERY 11 when a reboot was required and
otherwise MODULE FAILURE 11 when a failure was detected
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
7
module (for example, F8L).
7.2.2.3 Minor self-test error messages
Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
MODULE FAILURE___:
Contact Factory (xxx)
Latched target message: Yes.
Description of problem: Module hardware failure detected. Module Failures 12 and 31 to 33 are minor.
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
module (for example, F8L).
For Module Failure 31, a new process card hardware is available. The process card hardware has been enhanced to
support new features, such as fast distance protection, Synchrophasors Frequency, and Rate of Change of Frequency
calculations to conform to C37.118 - 2005 standard. The new functionality leveraging the hardware is supported with
firmware revision 7.25 and above. When using an older revision of the process card with a new firmware revision
7-8
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
.
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: COMMANDS AND TARGETS
setting indicates the G60 is not
to "Programmed."
.

Advertisement

Table of Contents
loading

Table of Contents