Teleprotection Inputs And Outputs - GE G60 Instruction Manual

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
:
"HYB POTT
DIRECT OUT 2 OPERAND
: "2"
DIRECT INPUT 5 DEVICE ID
DIRECT INPUT 5 BIT NUMBER
: "2"
DIRECT INPUT 6 DEVICE ID
DIRECT INPUT 6 BIT NUMBER
UR IED 2:
: "1"
DIRECT INPUT 5 DEVICE ID
DIRECT INPUT 5 BIT NUMBER
: "3"
DIRECT INPUT 6 DEVICE ID
DIRECT INPUT 6 BIT NUMBER
:
"HYB POTT
DIRECT OUT 2 OPERAND
:
"DIRECT INPUT
DIRECT OUT 3 OPERAND
:
"DIRECT INPUT
DIRECT OUT 4 OPERAND
The figure shows the signal flow among the three IEDs.
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 are ANDed in FlexLogic and the resulting operand configured as the permission to trip (
setting).

5.9.7 Teleprotection inputs and outputs

5.9.7.1 Overview
The relay provides 16 teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and 16
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only,
numbered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by
assigning FlexLogic operands to be sent via the selected communications channel. This allows the user to create
distributed protection and control schemes via dedicated communications channels. Some examples are directional
comparison pilot schemes and direct transfer tripping. Note that failures of communications channels affect
teleprotection functionality. The teleprotection function must be enabled to utilize the inputs.
5.9.7.2 Teleprotection inputs
SETTINGS  INPUTS/OUTPUTS  TELEPROTECTION  TELEPROT INPUTS
 TELEPROT INPUTS
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
TX1"
: "2" (this is a message from IED 2)
: "3" (effectively, this is a message from IED 1)
: "2"
: "2"
TX1"
5" (forward a message from 1 to 3)
6" (forward a message from 3 to 1)
Figure 5-207: Signal flow for direct input and output
TELEPROT INPUT 1-1
DEFAULT: Off
HYB POTT RX1
Range: Off, On, Latest/Off, Latest/On
INPUTS/OUTPUTS
5
5-349