Power Swing Detect (Ansi 68) - GE G60 Instruction Manual

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS

5.7.4 Power swing detect (ANSI 68)

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  POWER SWING DETECT
 POWER SWING
 DETECT
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-106: Phase distance logic
POWER SWING
FUNCTION: Disabled
POWER SWING
SOURCE: SRC 1
POWER SWING
SHAPE: Mho Shape
POWER SWING
MODE: Two Step
POWER SWING
SUPV: 0.600 pu
POWER SW I2 SUPV ENAB:
Off
POWER SWING
I2 SUPV: 0.200 pu
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Mho Shape, Quad Shape
Range: Two Step, Three Step
Range: 0.050 to 30.000 pu in steps of 0.001
Range: FlexLogic operand
Range: 0.050 to 30.000 pu in steps of 0.001