GE G60 Instruction Manual page 240

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

PRODUCT SETUP
Most of the settings are configured by drag-and-drop. However the ID, DEFAULT STATE, and EVENTS settings must be
individually entered when the factory default values are not acceptable.
RxGOOSE Boolean1 ID
Range: 0 to 20 characters
Default: RxG Bool1
This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The full
operand name is the value of this setting appended with " On". The standard and enhanced front panels display the first
17 characters of this setting plus " On" to fit the 20 character display.
RxGOOSE Boolean1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set to
None, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.
RxGOOSE Boolean1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member which does not contain a BOOLEAN results in the
RxGOOSE Boolean1 FlexLogic operand assuming its default state. The Subscribed to column identifies the particular
Boolean subscribed to even if the member is a structure containing more than one Boolean.
RxGOOSE Boolean1 DEFAULT STATE
5
Range: On, Off, Latest/On, Latest/Off
Default: Off
This setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup and
the selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with the
publisher. The following choices are available:
"On" value defaults the input to logic 1
"Off" value defaults the input to logic 0
"Latest/On" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 1. When communication resumes, the input
becomes fully operational.
"Latest/Off" freezes the input in case of lost connectivity. If the latest state is unknown, such as after UR power-up
but before the first communication, the input defaults to logic 0. When communication resumes, the input
becomes fully operational.
RxGOOSE Boolean1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE Boolean1 FlexLogic operand are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are never recorded, even if events are
enabled.
RxGOOSE DPS inputs
Navigate to Settings > Product Setup > Communications > IEC 618560 > GOOSE > RxGOOSE > RxGOOSE DPS Inputs.
There are Add IED and Remove IED buttons. The Add IED button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the
user select the ones to add.
5-64
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents