SYSTEM SETUP
— This setting selects an operand that creates a programmable signal to operate a contact output to close
SWITCH 1 CLOSE
disconnect switch 1.
SWITCH 1 BLK CLOSE
used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
SWTCH 1 ΦA/3P CLSD
position tracking mechanism. This input is a normally-open 89/a status input to create a logic 1 when the disconnect
switch is closed. If the
to track the disconnect switch open or closed position. If the mode is selected as "1-Pole," the input mentioned is used to
track phase A and the
SWTCH 1 ΦA/3P OPND
to create a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available, then an inverted
89/a status signal can be used.
SWITCH 1 ΦB CLOSED
pole, this input is used to track the disconnect switch phase B closed position as outlined for phase A.
SWITCH 1 ΦB OPENED
pole, this input is used to track the disconnect switch phase B opened position as outlined for phase A.
SWITCH 1 ΦC CLOSED
pole, this input is used to track the disconnect switch phase C closed position as outlined for phase A.
SWITCH 1 ΦC OPENED
pole, this input is used to track the disconnect switch phase C opened position as outlined for phase A.
SWITCH 1 TOPERATE
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
5
expired, the
SWITCH 1 BAD STATUS
SWITCH 1 ALARM DELAY
pole position tracking operands do not declare a pole disagreement. This allows for non-simultaneous operation of the
poles.
IEC 61850 functionality is permitted when the G60 is in "Programmed" mode and not in local control mode.
5-138
— This setting selects an operand that prevents closing of the disconnect switch. This setting can be
— This setting selects an operand, usually a contact input connected to a disconnect switch auxiliary
setting is selected as "3-Pole," this setting selects a single input as the operand used
SWITCH 1 MODE
and
SWITCH 1 ΦB
SWITCH 1 ΦC
— This setting selects an operand, usually a contact input, that is a normally-closed 89/b status input
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— This setting specifies the required interval to overcome transient disagreement between the 89/a
FlexLogic operand is asserted for alarm or blocking purposes.
— This setting specifies the delay interval during which a disagreement of status among the three-
settings select operands to track phases B and C, respectively.
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS