PRODUCT SETUP
RxGOOSE analog inputs
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Analog Inputs.
There are Add IED and Remove IED buttons. The Add IED button allows SCL files to be used, including ICD, CID, and SCD
(supported in version 7.40 and later). When the file format is SCD, the system lists all IEDs inside the SCD file and lets the
user select the ones to add.
5
There are 32 RxGOOSE analog inputs.
RxGOOSE Analog1 ID
Range: 0 to 20 characters
Default: RxG Analog1
This setting allows the user to assign descriptive text to RxGOOSE Analog1. Unlike RxGOOSE Booleans and RxGOOSE
DPS, the RxGOOSE Analog operands have fixed names, for example RxGOOSE Analog1.
RxGOOSE Analog1 RxGOOSE
Range: None, RxGOOSE1, RxGOOSE2, and so on
Default: None
This setting selects the GOOSE message that drives the RxGOOSE Analog1 FlexAnalog operand. If set to None, the
RxGOOSE Analog1 FlexAnalog operand assumes its default state.
RxGOOSE Analog1 Member
Range: 1 to 64 in steps of 1
Default: 1
This setting selects the GOOSE message member that drives the RxGOOSE Analog1 FlexAnalog operand. A setting of 1
selects the first member, 2 selects the second member, and so on. Entering a number greater than the number of
members in the message and entering the number of a member that does not contain a FLOAT32 results in the
RxGOOSE Analog1 FlexAnalog operand assuming its default state. The Subscribed to column identifies the particular
FLOAT32 subscribed to even if the member is a structure containing more than one FLOAT32.
5-66
Figure 5-23: RxGOOSE Analog Inputs panel
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS