Test Mode Forcing; Phasor Measurement Unit Test Values - GE G60 Instruction Manual

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS

5.11.2 Test mode forcing

SETTINGS  TESTING  TEST MODE FORCING
 TESTING
When in Forcible mode, the operand selected by the
testing conditions, as described in the following two sections.
The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED
indicator, and by the critical fail relay, as shown in the following table.
Table 5-45: Test mode operation
TEST MODE
In-service
FUNCTION
LED
Disabled
Unaffected
Isolated
Off
Forcible
Off
On restart, the
TEST MODE FORCING
their default states.

5.11.3 Phasor Measurement Unit test values

SETTINGS  TESTING  PMU TEST VALUES  PMU 1 TEST VALUES
 PMU 1
 TEST VALUES
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
TEST MODE FORCING:
On
TEST MODE FORCING
Test mode
Critical fail
TEST MODE
LED
relay
FORCING
Off
Normal
No effect
On
De-energized No effect
Flashing
De-energized Off
On
setting and the force contact input and force contact output settings revert to
PMU 1 TEST
FUNCTION: Disabled
PMU 1 VA TEST
MAGNITUDE: 500.00 kV
PMU 1 VA TEST
ANGLE: 0.00°
PMU 1 VB TEST
MAGNITUDE: 500.00 kV
PMU 1 VB TEST
ANGLE: –120.00°
PMU 1 VC TEST
MAGNITUDE: 500.00 kV
PMU 1 VC TEST
ANGLE: 120.00°
PMU 1 VX TEST
MAGNITUDE: 500.00 kV
PMU 1 VX TEST
ANGLE: 0.00°
PMU 1 IA TEST
MAGNITUDE: 1.000 kA
PMU 1 IA TEST
ANGLE: –10.00°
PMU 1 IB TEST
MAGNITUDE: 1.000 kA
Range:
FlexLogic operand
setting dictates further response of the G60 to
Contact input and output behavior
Normal
Contact outputs disabled
Normal
Controlled by forcing features
Range: Enabled, Disabled
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.00 to 700.00 kV in steps of 0.01
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
Range: –180.00 to 180.00° in steps of 0.05
Range: 0.000 to 9.999 kA in steps of 0.001
TESTING
5
5-363

Advertisement

Table of Contents
loading

Table of Contents