GE G60 Instruction Manual page 271

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
= (8191/(500000 * 2.4) ) * V - 4096 = 0.0068 * V - 4096
a = 0.0068
Since the step is in increments of 0.001, we round it at:
a = 0.006
b = -4096
Vt = 0.006 * V - 4096
For max voltage 500000 V * 2.4 = 1200000 V, we transmit
Vt = 0.006 * 1200000 - 4096 = 7200 - 4096 = 3104
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-103  IEC103 COMMANDS
 IEC103 COMMANDS
 COMMAND 0
 COMMAND 31
Commands are received as General Command (Type Identification 20). The user can configure the action to perform when
an ASDU command comes.
A list of available mappings is provided on the G60. This includes 64 virtual inputs (see the following table). The ON and OFF
for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-12: Commands mapping table
Description
Value
Off
0
Virtual Input 1
1
Virtual Input 2
2
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
 COMMAND 0
 COMMAND 1
 COMMAND 31
COMMAND 0 FUN:
0
COMMAND 0 INF:
0
COMMAND 0 ON:
Off
COMMAND 0 OFF:
Off
COMMAND 31 FUN:
0
COMMAND 31 INF:
0
COMMAND 31 ON:
Off
COMMAND 31 OFF:
Off
See below
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: Virtual input
Range: Virtual input
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: Virtual input
Range: Virtual input
PRODUCT SETUP
5
5-95