GE G60 Instruction Manual page 230

Generator protection system
Hide thumbs Also See for G60:
Table of Contents

Advertisement

PRODUCT SETUP
device displays a menu that lists the logical devices that this logical node can be moved to. Clicking one of these re-assigns
the logical node. Other common keyboard and/or mouse action can be used to select one or more logical nodes and move
the selected nodes together.
GOOSE
5
The path is Settings > Product Setup > Communications > IEC 61850 > GOOSE.
Support for Routable GOOSE
Routable GOOSE (R-GOOSE) is supported in firmware release 7.4 and later. Routable GOOSE allows UR and other devices to
be located in separate networks. Encryption/decryption of messages is performed by a separate gateway device.
Messages are routed using a separate router, using IP addresses.
Note the following behavior:
A v7.4 device can send an R-GOOSE message to another v7.4 device when both have R-GOOSE active as the protocol
A v7.4 device can send a GOOSE message to another v7.4 device when both have GOOSE active as the protocol
A v7.4 device cannot send an R-GOOSE message to non-R-GOOSE devices, such as v7.3 or v5.9 UR device
UR devices with firmware below v7.3 can send a GOOSE message to a v7.4 device that has GOOSE as the active
protocol
R-GOOSE is available through the IEC 61850 software option. If R-GOOSE security is required, the CyberSentry
software option also must be purchased.
TxGOOSE
IEC 61850 GOOSE is an efficient method for simultaneous high-speed delivery of generic substation event information by a
publishing device to more than one subscribing device. A TxGOOSE is a UR element implementing a single IEC 61850
GOOSE message publishing service. The subscribing function in URs is performed by RxGOOSE elements, as described in
the next section. Each UR with IEC 61850 order code options has 16 TxGOOSE elements. Each TxGOOSE can either use the
original format specified in IEC 61850 8 1:2011 or the routable GOOSE (R-GOOSE) format specified in IEC TR 61850-90-
5:2012. Each TxGOOSE element can publish the values of up to 64 attributes of the IEC 61850 nodes in the UR.
5-54
Figure 5-18: Move logical node
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL