Configuring the Power Mode
Power Inputs
1 input
Maximum Power Available for 3.5-kW Inputs (AC)
The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3.5-kW HVAC/HVDC power supplies depending on AC power
inputs, number of power supplies, and the mode used.
Cisco Nexus 7718 Switch Site Preparation and Hardware Installation Guide
92
Power Supplies
Combined Mode
1
3000 W
2
6000 W
3
9000 W
4
12000 W
5
15000 W
6
18000 W
7
21000 W
8
24000 W
9
27000 W
10
30000 W
11
33000 W
12
36000 W
13
39000 W
14
42000 W
15
45000 W
16
48000 W
Power Supply
Input Source
Redundancy
Redundancy
Mode
Mode
—
—
3000 W
3000 W
6000 W
3000 W
9000 W
6000 W
12000 W
6000 W
15000 W
9000 W
18000 W
9000 W
21000 W
12000 W
24000 W
12000 W
27000 W
15000 W
30000 W
15000 W
33000 W
18000 W
36000 W
18000 W
39000 W
21000 W
42000 W
21000 W
45000 W
24000 W
Managing the Switch
Full Redundancy
Mode
—
3000 W
3000 W
6000 W
6000 W
9000 W
9000 W
12000 W
12000 W
15000 W
15000 W
18000 W
18000 W
21000 W
21000 W
24000 W
OL-30453-01