Cisco Nexus 7718 Hardware Installation Manual page 121

Table of Contents

Advertisement

Installing or Replacing Modules, Fan Trays, and Power Supplies
You have up to 72 hours to replace one fan tray as long as the switch air-inlet temperature does not exceed
Note
86° Fahrenheit (30° C). If the temperature exceeds 86° Fahrenheit (30° C), the switch will shut down in
3 minutes. If you remove more than one fan tray at a time, the switch can operate up to three minutes
before shutting down. To prevent a shutdown, remove only one fan tray at a time.
Fan Tray Maintenance Mode
Starting from Cisco NX-OS Release 7.2(0)D1(1), use the hardware fan-tray maintenance-mode [long |
medium | short] command to prepare a switch for fan tray removal. By default, the fans run at 100 percent
speed for approximately 4 minutes to prepare for fan tray removal when the hardware fan-tray
maintenance-mode command is used. Starting from Cisco NX-OS Release 8.1(1), by default, the fans run
at 85 percent speed for approximately 4 minutes to prepare for fan tray removal when the hardware fan-tray
maintenance-mode command is used.
Use the long keyword to run the fans at 65 percent speed for approximately 9 minutes to prepare for fan tray
removal. Use the medium keyword to run the fans at 75 percent speed for approximately 6 minutes to prepare
for fan tray removal. Use the short keyword to run the fans at 85 percent speed for approximately 4 minutes
to prepare for fan tray removal. For more information about the hardware fan-tray maintenance-mode, see
Cisco Nexus 7000 Series NX-OS System Management Command
The fan tray maintenance mode will be cancelled in the following cases:
• If a temperature alarm is present.
• Hot-inlet temperature (Sup inlet temperature >= 30 degrees Celsius)
• Fan-tray is absent.
• Post-cool period (time elapsed after fan tray removal) has crossed 4 minutes.
• Pre-cool period (time elapsed before fan tray removal) has crossed 1 hour and 9 minutes—The fan tray
has not been removed since the past 1 hour and 9 minutes during which the switch was ready for fan
tray removal.
The following example shows the syslogs that are generated when the fan speed increases due to a minor
temperature alarm:
2017 Apr 3 16:46:07 SWITCH %CARDCLIENT-2-SSE: XBAR:5 FABRIC ONLINE
2017 Apr 3 16:46:07 SWITCH %PLATFORM-5-MOD_STATUS: Fabric-Module 5 current-status is
MOD_STATUS_ONLINE/OK
2017 Apr 3 16:46:07 SWITCH %MODULE-5-XBAR_OK: Xbar 5 is online (Serial number: JAE1921079X)
2017 Apr 3 16:47:00 SWITCH %PLATFORM-2-MOD_TEMPMINALRM: Xbar-5 reported minor temperature
alarm. Sensor=1 Temperature=48 MinT
hreshold=20
2017 Apr 3 16:47:00 SWITCH %VSHD-5-VSHD_SYSLOG_CONFIG_I: Configured from vty by admin on
vsh.12644
2017 Apr 3 16:47:35 SWITCH %PLATFORM-6-PFM_INFO: Fan Zone 1 : Fan Speed will change from
45.88(0x75) to 54.12(0x8a)
2017 Apr 3 16:54:50 SWITCH %PLATFORM-2-PFM_MODULE_POWER_OFF: Manual power-off of Xbar 5
OL-30453-01
Fan tray maintenance mode is cancelled and fan speed is set to normal if fan tray
Note
migration or replacement is completed within 2 minutes of using the hardware fan-tray
maintenance-mode command. If fan tray migration or replacement is not completed
within 2 minutes, the remaining fan trays run at 85 percent speed for the next 2 minutes,
and at 100 percent speed from then on.
Cisco Nexus 7718 Switch Site Preparation and Hardware Installation Guide
Replacing a Fan Tray
Reference.
111