Managing the Switch
To display the current power supply configuration, use the show environment power command.
Note
Procedure
Step 1
Start the configuration mode by entering the configure terminal command.
Example:
switch# configure terminal
switch(config)#
Step 2
Specify one of the following power modes by entering the power redundancy-mode mode command:
• For combined mode, include the combined keyword.
• For power supply redundancy mode, include the ps-redundant keyword.
• For input source redundancy mode, include the insrc_redundant keyword.
• For full redundancy mode, include the redundant keyword.
Example:
switch(config)# power redundancy-mode redundant
switch(config)#
Maximum Power Available for 3-kW Power Supplies
The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3-kW power supplies depending on power inputs, numbers of
power supplies, and the mode used.
OL-30453-01
Cisco Nexus 7718 Switch Site Preparation and Hardware Installation Guide
Configuring the Power Mode
89