Page 4
FIGURE 22: SURFACE MOUNTING DIFC......................... 31 FIGURE 23: DSFC PANEL MOUNTING AND DRILLING ..................32 FIGURE 25: DIAC OR DSFC TEST SETUP FOR PICKUP AND OPERATING TIME VERIFICATION ..... 37 FIGURE 26: DIFC TEST SETUP FOR INSTANTANEOUS UNIT................37 FIGURE 27: DIAC OR DSFC TEST SETUP FOR INSTANTANEOUS............... 38 FIGURE 28 (9819647/8919648): DIAC FRONT AND REAR VIEWS .................
• Fully Retrofitable * • Functional separate TOC and IOC opera- tions. • Wide settings range. To Load • Drawout case construction When replacing unit and case (see instruction manual INSTALLATION section for details). DIAC / DIFC / DSFC Digital Overcurrent Protection...
The DIAC, DIFC and DSFC are a family of self- less than 7%. powered, single-phase, digital overcurrent relays. The DIAC is packaged in a GE S1 style case, the The relays contain two independent settings, one DIFC is packaged in a GE C1 style case and the for TOC and one for IOC.
Page 7
IEEE Inverse See Figure 12 for graph of equation − Reset time − − Pickup time 0103 0228 − DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) Inverse Standard 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 1: IAC51 TOC Curve DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) Very Inverse Standard 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 2: IAC53 TOC Curves DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) Short Time 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 3: 55 Short Time TOC Curves DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) Inverse Medium 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 4: 57 Medium Time TOC Curves DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) Inverse Long 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 5: 66 Long Time TOC Curves DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) 0.1 - 3.18 (1 Ampere Relays) Inverse Medium Short General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 6: 75 Short Time TOC Curves DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) Inverse Short 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 8: 95 Short Time TOC Curves DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 10: IEC Very Inverse TOC Curves DIAC / DIFC / DSFC Digital Overcurrent Protection...
Current Range: 0.5 - 15.9 ( 5 Ampere Relays) Very Inverse 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 13: IEEE Very Inverse TOC Curves DIAC / DIFC / DSFC Digital Overcurrent Protection...
Time Dial Range: (0.5 - 9.9) Definite Time Current Range: 0.5 - 15.9 ( 5 Ampere Relays) 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 15: Definite Time DIAC / DIFC / DSFC Digital Overcurrent Protection...
Time Dial Range: (0.5 - 9.9) Current Range: 0.5 - 15.9 ( 5 Ampere Relays) 0.1 - 3.18 (1 Ampere Relays) General Electric CO., 205 Great Valley Parkway, Malvern, PA 19355 Figure 16: I t Time Curve DIAC / DIFC / DSFC Digital Overcurrent Protection...
The system frequency can be set for 50 or 60 Hz element. The time dial can be set from 0.5 to 9.9 controlled from the front panel. in 0.1 increments on both the 5 amp model and DIAC / DIFC / DSFC Digital Overcurrent Protection...
DIAC and DSFC minimum setting. The DIAC and DSFC relays consist of a case, The relay also provides a front panel trip circuit cover, support structure, and a connection plug test. An actuating lever that must be pulled and to make up the electrical connection.
Reset And Manual Trip Cover Installation DIAC and DSFC Targets can be reset by depressing the front NOTE: When replacing the cover on the DIAC cover target reset button for the DIFC or lifting and DSFC relays the reset wire should be the target reset level at the lower left edge of the “locked”...
12 AWG braided ground lead connected to Terminal 4 when replacing IFC relays. The IFC relay and case must be removed and replaced with the DIFC relay and case. DIAC / DIFC / DSFC Digital Overcurrent Protection...
FOR SURFACE MOUNTING FRONT VIEW FRONT VIEW CASE 5/16-18 STUD TYPICAL DIM. 76MM INCHES VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG. ON STEEL PANELS Figure 20: DIAC Panel Mounting and Drilling DIAC / DIFC / DSFC Digital Overcurrent Protection...
FOR SEMI-FLUSH MOUNTING FRONT VIEW FRONT VIEW CASE 5/16-18 STUD TYPICAL DIM. 76MM INCHES VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG. ON STEEL PANELS Figure 23: DSFC Panel Mounting and Drilling DIAC / DIFC / DSFC Digital Overcurrent Protection...
*(.& ACCEPTANCE TESTS Immediately upon receipt of the relay, an use the XLA series test plug (refer to the GE inspection and acceptance test should be made Power Management Product Catalog). Although to make sure that no damage has been...
Page 38
Single Phase Current Source AUX TOC contact – Negative 36/300VDC Power Supply Target and Current Limited to Seal-in 200 mA + Positive Figure 24: DIFC Test Setup for Pickup and Operating Time Verification DIAC / DIFC / DSFC Digital Overcurrent Protection...
36 / 300 V DC Power Supply Target and I in Current Limited to Seal-In 200 mA + Positive Figure 25: DIAC or DSFC Test Setup for Pickup and Operating Time Verification Start Stop TIMER Single Phase Current Source AUX TOC Contact...
AUX TOC Contact - Negative 36 / 300 V DC Power Supply Target and I in Current Limited Seal-In to 200 mA + Positive Figure 27: DIAC or DSFC Test Setup for Instantaneous DIAC / DIFC / DSFC Digital Overcurrent Protection...
*(.& Figure 29 (8919652/8919653): DIFC Front and Rear Views Figure 30 (8919632/8919661): DSFC Front and Rear Views DIAC / DIFC / DSFC Digital Overcurrent Protection...
The trip contact remains closed until the trip circuit drops below 0.19 A. A breaker contact + DC Supply Breaker Contact (52a) Trip Coil - DC Supply Figure 32: IOC/TOC UNIT DIAC / DIFC / DSFC Digital Overcurrent Protection...