Using the High-Speed Counter and Programmable Limit Switch
HSL - High-Speed
Counter Load
HSL
HSL
High Speed Counter Load
HSC Number
HSC0
High Preset
N7:0
Low Preset
N7:1
Output High Source
N7:2
Output Low Source
N7:3
HSL Instruction Valid Addressing Modes and File Types
For definitions of the terms used in this table see Using the Instruction Descriptions on page 82.
Parameter
Counter Number
High Preset
•
•
•
Low Preset
•
•
•
Output High Source
•
•
•
Output Low Source
•
•
•
Publication 1763-RM001C-EN-P - October 2009
Instruction Type: output
Controller
Data Size
MicroLogix 1100
word
long word
The HSL (High-Speed Load) instruction allows the high and low presets,
and high and low output source to be applied to a high-speed counter.
These parameters are described below:
• Counter Number - Specifies which high-speed counter is being
used; 0 = HSC0 and 1 = Not support.
• High Preset - Specifies the value in the high preset register. The data
ranges for the high preset are -32768 to 32767 (word) and
-2,147,483,648 to 2,147,483,647 (long word).
• Low Preset - Specifies the value in the low preset register. The data
ranges for the low preset are -32768 to 32767 (word) and
-2,147,483,648 to 2,147,483,647 (long word).
• Output High Source - Specifies the value in the HPO - high preset
output register. The data range for the output high source is from 0
to 65,535.
• Output Low Source - Specifies the value in the LPO - low preset
output register. The data range for the output low source is from 0
to 65,535.
Valid Addressing Modes and File Types are shown below:
Data Files
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Execution Time When Rung Is:
True
False
82.37 μs
0.87 μs
84.37 μs
0.87 μs
Function Files
Address
Address Level
Mode
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•