How Counters Work - Allen-Bradley MicroLogix 1100 Instruction Set Reference Manual

Hide thumbs Also See for MicroLogix 1100:
Table of Contents

Advertisement

efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive
174
Timer and Counter Instructions

How Counters Work

Publication 1763-RM001C-EN-P - October 2009
The figure below demonstrates how a counter works. The count value
must remain in the range of -32,768 to +32,767. If the count value goes
above +32,767, the counter status overflow bit (OV) is set (1). If the count
goes below -32,768, the counter status underflow bit (UN) is set (1). A
reset (RES) instruction is used to reset (0) the counter.
-32,768
Underflow
Using the CTU and CTD Instructions
Counter instructions use the following parameters:
• Counter - This is the address of the counter within the data file. All
counters are 3-word data elements. Word 0 contains the Control and
Status Bits, Word 1 contains the Preset, and Word 2 contains the
Accumulated Value.
Word
Bit
15 14 13 12 11 10 9
Word 0
CU CD DN OV UN Not Used
Word 1
Preset Value
Word 2
Accumulated Value
CU = Count Up Enable Bit
CD = Count Down Enable Bit
DN = Count Done Bit
OV = Count Overflow Bit
UN = Count Underflow Bit
• Preset - When the accumulator reaches this value, the DN bit is set.
The preset data range is from -32768 to 32767.
• Accumulator - The accumulator contains the current count. The
accumulator data range is from -32768 to 32767.
The accumulated value is incremented (CTU) or decremented (CTD)
on each false-to-true rung transition. The accumulated value is
retained when the rung condition again becomes false, and when
power is cycled on the controller. The accumulated count is
0
Count Up
Counter Accumulator Value
Count Down
8
7
6
+32,767
Overflow
5
4
3
2
1
0