Allen-Bradley MicroLogix 1100 Instruction Set Reference Manual page 165

Hide thumbs Also See for MicroLogix 1100:
Table of Contents

Advertisement

efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive
OSR and OSF Instructions Valid Addressing Modes and File Types
For definitions of the terms used in this table see Using the Instruction Descriptions on page 82.
Parameter
Storage Bit
Output Bit
These instructions use two parameters, Storage Bit and Output Bit.
• Storage Bit - This is the bit address that remembers the rung state
from the previous scan.
• Output Bit - This is the bit address which is set based on a
false-to-true (OSR) or true-to-false (OSF) rung transition. The Output
Bit is set for one program scan.
To re-activate the OSR, the rung must become false. To re-activate the
OSF, the rung must become true.
OSR Storage and Output Bit Operation
Rung State Transition
false-to-true (one scan)
true-to-true
true-to-false and false-to-false
OSF Storage and Output Bits Operation
Rung State Transition
true-to-false (one scan)
false-to-false
false-to-true and true-to-true
Addressing Modes and File Types can be used as shown in the following
table:
Data Files
Relay-Type (Bit) Instructions
Storage Bit
bit is set
bit is set
bit is reset
Storage Bit
bit is reset
bit is reset
bit is set
Function Files
Publication 1763-RM001C-EN-P - October 2009
165
Output Bit
bit is set
bit is reset
bit is reset
Output Bit
bit is set
bit is reset
bit is reset
Address
Address Level
Mode

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1763-l16bbb1763-l16awa1763-l16bwa1763-l16dwd

Table of Contents