Communications Instructions
MSG Instruction Error
Codes
Error Code
Description of Error Condition
02H
Target node is busy. NAK No Memory retries by link layer exhausted.
03H
Target node cannot respond because message is too large.
04H
Target node cannot respond because it does not understand the command parameters OR the control block may have been
inadvertently modified.
05H
Local processor is off-line (possible duplicate node situation).
06H
Target node cannot respond because requested function is not available.
07H
Target node does not respond.
08H
Target node cannot respond.
09H
Local modem connection has been lost.
0BH
Target node does not accept this type of MSG instruction.
0CH
Received a master link reset (one possible source is from the DF1 master).
0FH
DCOMM button was activated while an ASCII instruction was waiting to execute.
10H
Target node cannot respond because of incorrect command parameters or unsupported command.
12H
Local channel configuration protocol error exists.
13H
Local MSG configuration error in the Remote MSG parameters.
15H
Local channel configuration parameter error exists.
16H
Target or Local Bridge address is higher than the maximum node address.
17H
Local service is not supported.
18H
Broadcast is not supported.
20H
PCCC Description: Host has a problem and will not communicate.
21H
Bad MSG file parameter for building message.
30H
PCCC Description: Remote station host is not there, disconnected, or shutdown.
37H
Message timed out in local processor.
39H
Local communication channel reconfigured while MSG active.
3AH
STS in the reply from target is invalid.
40H
PCCC Description: Host could not complete function due to hardware fault.
45H
MSG reply cannot be processed. Either Insufficient data in MSG read reply or bad network address parameter.
50H
Target node is out of memory.
60H
Target node cannot respond because file is protected.
70H
PCCC Description: Processor is in Program Mode.
80H
PCCC Description: Compatibility mode file missing or communication zone problem.
81H
Modbus Error 1: Illegal Function
82H
Modbus Error 2: Illegal Data Address
83H
Modbus Error 3: Illegal Data Value
84H
Modbus Error 4: Slave Device Failure
85H
Modbus Error 5: Acknowledge
86H
Modbus Error 6: Slave Device Busy
87H
Modbus Error 7: Negative Acknowledge
88H
Modbus Error 8: Memory Parity Error
89H
Modbus Error: Non-standard reply. Actual code returned can be found in the upper byte of sub-element 22.
90H
PCCC Description: Remote station cannot buffer command.
Publication 1763-RM001B-EN-P - April 2007
When the processor detects an error during the transfer of message data,
the processor sets the ER bit and enters an error code that you can
monitor from your programming software.