The following ladder logic will need to be entered into File #2
By toggling Bit B3/0 the PTO can be activated. Once running the PTO will
generate the number of pulses entered into the PTO:0.TOP word and then
stop. To restart, toggle B3/0.
General Information on the PTO
Once running the PTO will continue to generate pulses until all pulses
have been generated or the PTO:0/EH (Enable Hard Stop) bit has been
activated.
Once the EH bit is set the instruction will generate a PTO error of 1 (hard
stop detected). In order to clear this error the PTO instruction must be
scanned on a false rung of logic, and the EH bit must be off.
To change the Total Output Pulses Generated in a working program a
new value can be moved into PTO:0.TOP by using the MOV command.
Important Note: Once the PTO has been initiated and is generating
pulses a new TOP value will not take effect until the PTO has either
completed generating pulses and has been restarted or has been Hard
Stopped using PTO:0/EH bit and been restarted.
Publication 1763-RM001C-EN-P - October 2009