DF1 Half-Duplex Master MSG-based Polling Mode Operation
With MSG-based Polling Mode, the master device only initiates
communication with a slave when a MSG instruction to that slave is
triggered in ladder logic. Once the read or write command has been
transmitted, the master waits the Reply MSG Timeout period and then
polls that slave for a reply to its command. The master can be configured
either to ignore ("MSG-based Polling, don't allow slaves to initiate") or to
accept ("MSG-based Polling, allow slaves to initiate") MSGs that may have
been triggered and queued up in the slave.