Ascii Driver - Allen-Bradley MicroLogix 1100 Instruction Set Reference Manual

Hide thumbs Also See for MicroLogix 1100:
Table of Contents

Advertisement

efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive
534
Protocol Configuration

ASCII Driver

Publication 1763-RM001C-EN-P - October 2009
The ASCII driver provides connection to other ASCII devices, such as bar
code readers, weigh scales, serial printers, and other intelligent devices.
You can use ASCII by configuring the RS-232 port, channel 0 for ASCII
driver. When configured for ASCII, all received data is placed in a buffer.
To access the data, use the ASCII instructions in your ladder program. See
ASCII Instructions on page 309 for information on using the ASCII
instructions. You can also send ASCII string data to most attached devices
that accept ASCII data/characters.
Only ASCII instructions can be used when a channel is
NOTE
configured for ASCII. If you use a Message (MSG)
instruction that references the channel, an error occurs.
The channel configuration screen is shown below:
The controller updates changes to the channel configuration at the next
execution of a Service Communications (SVC) instruction, I/O Refresh
(REF) instruction, or when it performs Communications Servicing,
whichever comes first.

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MicroLogix 1100 and is the answer not in the manual?

This manual is also suitable for:

1763-l16bbb1763-l16awa1763-l16bwa1763-l16dwd

Table of Contents

Save PDF