Panasonic S-36PU1E5A Service Manual page 645

Table of Contents

Advertisement

Item code
Item
Automatic drain pump
operation
Ventilation fan operation
Wired remote controller
sensor
"Operation change control in
progress" display
OFF reminder function for
when weekly timer is used
Heat exchanger temperature
for cold air discharge
(Heat exchanger control
point for control to prevent
cold air)
Fan output switching
Drain pump delayed start
time
Humidifier setting
Flap operation mode
Flap swing mode
No.
0000
No forced operation
0001
Forced operation for 1 minute
Continuous operation
0060
None
0000
0001
Ventilation fan operated by remote controller.
0000
Not used. (Body sensor is used.)
Remote control sensor is used.
0001
Normal (displayed)
0000
Not displayed
0001
0000
None
0001
Only stop time setting is enabled.
0008
Control temperature 8°C
0009
Control temperature 9°C
0025
Control temperature 25°C
0026
Control temperature 26°C
0000
Output linked with fan. (ON when indoor unit fan is operating.)
0001
Fan mode operation output
0000
No delayed start
0001
1 minute delayed start
0002
2 minutes delayed start
0058
58 minutes delayed start
0059
59 minutes delayed start
0060
60 minutes delayed start
0000
Humidifier output OFF. Drain pump stopped.
0001
Humidifier output ON. Drain pump operates.
Humidifier output ON. Drain pump operates for 1 minute when
0002
total humidifier operating time reaches 60 minutes.
0003
Humidifier output ON. Drain pump stopped.
0000
Standard setting
Draft reduction mode (Flap lower-limit position is shifted
0001
upwards.)
Smudging reduction mode (Flap swing upper-limit position is
0000
shifted downwards.)
0001
Normal mode
Draft reduction mode (Flap swing lower-limit position is shifted
0002
upwards.)
7-9
Setting data
Description