Room Temperature Control - Panasonic S-36PU1E5A Service Manual

Table of Contents

Advertisement

4-1. Room Temperature Control

The body sensor or remote controller sensor detects temperature in the room. The detected temperature is
called the room temperature. The body sensor is the one contained in the indoor unit.
Set temp.
Detected temp. by
sensor
Room temp.
The thermostat is turned ON or OFF according to the following T.
T (Cooling)
T (Heating)
Correction temperature (only during heating)
If the indoor unit is installed on the ceiling, temperature near the ceiling is higher than near the floor. When
the body sensor is enabled, lower temperature near the floor must be considered. To correct this difference in
4
temperature, the correction temperature is used.
The factory setting for the correction temperature is different depending on the model. Refer to "4-11. Parameter".
Example: Cooling temperature correction
4-Way Cassette (correction temperature: 0 degrees)
Body sensor is enabled
Set temp. in remote
controller
Detected temp. by
sensor
Detected temp. by
body sensor
Detected temp. by
remote controller
sensor
Room temp. = temp.
detected by body
sensor
T
Body sensor is enabled
Set temp. in remote controller
Detected temp. by body sensor
Detected temp. by body sensor -
*correction temp.
T = room temp. – set temp. (set temp. in remote controller)
T = set temp. – room temp.
28
28
28
30.0
27.5
27.0
30.0
27.5
27.0
30.0
27.5
27.0
30.0
27.5
27.0
=30.0
=27.5
=27.0
+2.0deg -0.5deg -1.0deg
Thermostat
Thermostat
Thermostat
ON
ON
OFF
Remote controller sensor is enabled
Set temp. in remote controller
Detected temp. by remote controller
sensor
Detected temp. by remote controller
sensor
Example: Heating temperature correction
4-Way Cassette (correction temperature: 4 degrees)
Body sensor is enabled
Set temp. in remote
controller
Detected temp. by
sensor
Detected temp. by
body sensor
Detected temp. by
remote controller
sensor
Room temp. = temp.
detected by body
sensor – 4 deg
T
4-2
20
20
20
17.0
22.0
25.0
17.0
22.0
25.0
13.0
18.0
21.0
13.0
18.0
21.0
=17.0-4
=22.0-4
=25.0-4
deg
deg
deg
+7.0deg +2.0deg -1.0deg
Thermostat
Thermostat
Thermostat
ON
ON
OFF

Hide quick links: