E05 Error in Indoor Unit Transmitting Signal to the Outdoor Unit
1.
Error Detection Method
It is judged an error when a unit itself cannot receive a signal that it has sent.
Indoor unit control PC board error
The setting of the terminal resistor select switch on the outdoor unit main PC board is set incorrectly.
2.
Error Diagnosis
1 Indoor
Is the indoor/outdoor operation line connected to more than one
1-1
unit
outdoor unit? (Network wired?)
control
Is the SHORT on the terminal resistor select switch on the outdoor
PC board
1-2
main PC board set to one unit, and the others are OPEN?
Is the terminal resistor select switch on the outdoor main PC board
1-3
set to OPEN?
1-4
Is the indoor/outdoor operation line opened or shorted?
1-5
Replace the indoor unit control PC board.
For information on the procedures for replacing the indoor unit's control PC board, refer to the manual that is packaged with
the indoor unit service board.
CR-50PE1E5 : Up side (U-50PE1E5)
(for single-phase outdoor unit PCB)
EEPROM
TERMINAL
A747898 : (U-60PE1E5A, U-71PE1E5A)
(for single-phase outdoor unit PCB)
TERMINAL
5-17
Yes
1-2
No
1-3
Yes
1-4
Set the SHORT to
No
one unit only
Make the SHORT
Yes
setting
No
1-4
Yes
Correct the wiring
No
1-5
EEPROM