E05 Error in Indoor Unit Transmitting Signal to the Outdoor Unit
1.
Error Detection Method
It is judged an error when a unit itself cannot receive a signal that it has sent.
Indoor unit control PC board error
•
•
The setting of the terminal resistor select switch on the outdoor unit main PC board is set incorrectly.
2.
Error Diagnosis
1 Indoor
Is the indoor/outdoor operation line connected to more than one
1-1
unit
outdoor unit? (Network wired?)
control
Is the SHORT on the terminal resistor select switch on the outdoor
PC board
1-2
main PC board set to one unit, and the others are OPEN?
Is the terminal resistor select switch on the outdoor main PC board
1-3
set to OPEN?
1-4
Is the indoor/outdoor operation line opened or shorted?
1-5
Replace the indoor unit control PC board.
•
For information on the procedures for replacing the indoor unit's control PC board, refer to the manual that is packaged with
the indoor unit service board.
CR-50PE1E5 : Up side (U-50PE1E5)
(for single-phase outdoor unit PCB)
EEPROM
TERMINAL
A747898 : (U-60PE1E5A, U-71PE1E5A)
(for single-phase outdoor unit PCB)
TERMINAL
5-17
Yes
1-2
No
1-3
Yes
1-4
Set the SHORT to
No
one unit only
Make the SHORT
Yes
setting
No
1-4
Yes
Correct the wiring
No
1-5
EEPROM
5