1
Automatic Address Setting
Basic wiring diagram
Link wiring
NOTE
A terminal plug (black) is attached to each of the outdoor unit control PCBs.
At only 1 outdoor unit, leave the terminal plug short-circuit socket on the "Yes" side.
At all the other outdoor units, change the socket (from "Yes" to "No").
A maximum of 8 indoor units can be connected to 1 remote controller for group control.
Outdoor unit
Terminal board 1, 2
Terminal board 1, 2
Indoor unit
Wireless remote controller
If wall mounted type units are used for a simultaneous-operation multi system (group control), refer to
*
section "System Control" for Type K1.
System Control (basic wiring diagrams and wiring procedures) when wiring.
Setting the outdoor unit system addresses
For basic wiring diagram (Set the system addresses: 1, 2, 3...)
Outdoor unit control PCB
System address rotary switch
(Set to "0" at time of shipment)
System address
rotary switch
System address
System address 1
(Change setting to "1")
No. 1
Inter-unit
control
wiring
1-1
1-2
Remote control communication
wiring for group control
10s 20s
DIP switch
ON
ON
1
2
OFF
System address 2
(Change setting to "2")
Change the terminal
plug (black) short-
circuit socket
No. 2
2-1
2-2
Wired remote
controller
Remote control communication
wiring for group control
HIC
Temperature
sensor
Up side
C2(CN020,WHT)
MOV(CN025,WHT)
63PH(CN004,RED)
Bottom
side
1-318
System address 3
(Change setting to "3")
Change the terminal
plug (black) short-
circuit socket
No. 3
Inter-unit control
wiring
3-1
3-2
Wired
remote
controller
AUTO ADD(CN041)
System address
Rotary switch(S002)
TERMINAL (CN003)
JP007
System address
DIP switch (S003)
RC-P(CN032,RED)
LED1
LED2
PUMP DOWN(CN042)
EEPROM(IC006)
C1(CN021,BLK)
TO(CN022,WHT)
TD,TS(CN023,WHT)
SILENT MODE(CN028,WHT)
RC-P(CN034,RED)
FAN(CN030,WHT)
ROM(CN012,WHT)
OC(CN013,BLU)
EMG(CN014,BRN)
20S(CN09,WHT)
FUSE(30A,F003)