Panasonic S-36PU1E5A Service Manual page 595

Table of Contents

Advertisement

H03 Primary Current CT Sensor (current sensor) Failure
1.
Error Detection Method
It is judged an error based on the criteria listed below.
If 18A or greater is detected when the compressor is stopped (alarm triggered even if the connector is unplugged).
If no current is detected even though a compressor is running.
2.
Error Diagnosis
1 Check the
Turn the power on again and run the outdoor unit.
1-1
control
Is alarm occurred after operation?
PC board
5-39
Yes
Replace CR board.
No
See what happens.
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents