Panasonic S-36PN1E5A Installation Instructions Manual

Hide thumbs Also See for S-36PN1E5A:

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic S-36PN1E5A

  • Page 2: Please Read Before Starting

    IMPORTANT! When Transporting Please Read Before Starting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to This air conditioner must be installed by the sales dealer or reduce strain on your back.
  • Page 3 When Servicing • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. • Keep your fingers and clothing away from any moving parts. • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
  • Page 4 Page IMPORTANT ..................2 7. HOW TO INSTALL WIRELESS REMOTE CONTROLLER RECEIVER ................24 Please Read Before Starting 1. GENERAL ................... 5 NOTE 1-1. Tools Required for Installation (not supplied) Refer to the Operating Instructions attached to the optional Wireless Remote Controller Receiver. 1-2.
  • Page 5 1. GENERAL Table 1-1 (Ducted) Part Name Figure Q’ty Remarks This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions For suspending indoor unit for the indoor and outdoor units and make sure all accessory parts Washer from ceiling listed are with the system before beginning.
  • Page 6: Selecting The Installation Site

    2. SELECTING THE INSTALLATION SITE 2-1. Indoor Unit AVOID:  areas where leakage of fl ammable gas may be expected.  places where large amounts of oil mist exist.  direct sunlight.  locations near heat sources which may affect the performance of the unit.
  • Page 7 Install the unit leaning to a drainage hole side as a figure for easy water drainage. 1~3mm Drainage hole (Unit:mm) Caution TYPE Remove the absorber at air return S-36PN1E5A hole before installation. S-45PN1E5A 840 780 523 S-50PN1E5A S-60PN1E5A 1060 1000 523 S-71PN1E5A...
  • Page 10 Unit:mm Fig.3-2...
  • Page 11 3-2. Suspending the Indoor Unit Suspension bolt Depending on the ceiling type: • Insert suspension bolts (Fig. 3-3) Hexagonal nut Double nuts • Use existing ceiling supports or construct a suitable support (Fig. 3-4). Hole-in-anchor Fig.3-6 Hole-in-plug Concrete Insert  This shows an example of installation.
  • Page 12 3-3. Installing the Drain Pipe Drainage hole (1) Prepare standard hard PVC pipe (O.D. 32 mm) for the drain and use the supplied hose band to prevent water leaks. The PVC pipe must be purchased separately. Thermal insulator Hose clip (Accessories) (Accessories) Fig.3-11...
  • Page 13 3-5. External Static Pressure Setting for Dc Fan Motor Model Choose one of the following methods from “a”, “b”, “c” or “d” as shown in the flow chart (within the dotted lines) and then make the setting accordingly. a. No setting modification ................. : Use-as-is at shipment (there are cases in which the setting may differ from the shipment setting when reset after once setting the external static pressure.) b.
  • Page 14 (3) Refer to Table 3-4 and Fig. 3-18 for details on the relationship between the value of item code “b0” and the external static pressure. (4) When set in group control (connecting multiple indoor units with one wired remote controller), set each indoor unit to item code “b0”. When amending the setting after selecting [ b.
  • Page 15 3-5-2. Operating the Timer Remote Controller (CZ-RTC2) Table 3-4 Setting the external static pressure Indoor unit Item code 3-6-2-1. Setting Item Code “ ” 60, 71 100, 125, 140 Press and hold down the buttons simultaneously for 4 or more seconds. External static pressure of the rated air , the Unit No., Item Code and Detailed Data will blink flow volume (Pa)
  • Page 16: Indoor Fan Performance

    Indoor Fan Performance Item code “ ” M M M M M M M L L L L L L L L L L L L 1 -2 1 -3 S-125PN1E5 S-60PN1E5 ,S-71PN1E5 P-Q diagram P-Q diagram Limit line Limit line Air Volume (m /min.) Air Volume (m...
  • Page 17 3-6. External Static Pressure Setting for AC Fan Motor Model To apply to following models  S-36PN1E5 , S-45PN1E5 , S-50PN1E5 There are two tap connector located in indoor unit control box can be selected. The “blue connector” is standard tap ,use-as-is at shipment. For high static pressure duct, switch Fan Motor connector to plug in boost tap “white connector”...
  • Page 18: Electrical Wiring

    4. ELECTRICAL WIRING 4-1. General Precautions on Wiring (1) Before wiring, confi rm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit and a circuit breaker for overcurrent protection should be provided in the exclusive line.
  • Page 19 4-3. Wiring System Diagrams * 3-phase model connections Indoor unit (No.1) Power supply Outdoor unit (3-phase) 220/230/240V ~50Hz INV unit Ground Power supply Remote 380 – 415 V, 3 N~ 50Hz controller Ground Ground * Single-phase model connections Indoor unit (No.1) Power supply Outdoor unit (single-phase)
  • Page 20 CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.