H01 Primary (input) Overcurrent Detected
1.
Error Detection Method
Primary current effective value detected overcurrent (trip current value).
Trip current value
Single-phase model
Heating
Cooling
2.
Error Diagnosis
1 Power
Not satisfied with + 10% rated supply voltage
1-1
supply*
1-2
Extreme voltage fluctuations
1-3
Extreme distortion of voltage waveform
1-4
Instantaneous blackout may sometimes occur.
2
PC board
Has FUSE 1/FUSE 2 blown?
2-1
wiring
Check the electrical conduction with tester.
2-2
Loose electrical wire connection
2-3
Replace CR board.
*
Check not only in the outdoor unit stop mode but in the drive mode.
CR-50PE1E5 : bottom (U-50PE1E5)
(for single-phase outdoor unit PCB)
F001
hp = horse power
2.5 hp
3 hp
4 hp
20.0A
20.0A
27.0A
29.0A
18.5A
18.5A
27.0A
29.0A
Trip current value
5 hp
6 hp
3-phase model
30.0A
Heating
30.0A
Cooling
A747898 : (U-60PE1E5A, U-71PE1E5A)
(for single-phase outdoor unit PCB)
5-35
hp = horse power
4 hp
5 hp
6 hp
12.5A
13.5A
14.5A
12.0A
12.6A
13.0A
Yes
Check power supply
No
1-2
Yes
Check power supply
No
1-3
Yes
Check power supply
No
1-4
Yes
Check power supply
No
2-1
2-3
Yes
No
2-2
Yes
Correct wiring
No
2-3
FUSE1
5