Panasonic S-36PU1E5A Service Manual page 312

Table of Contents

Advertisement

1
Test Run
Using the control unit
(1) Change the indoor control unit switch from "ON" → "TEST".
(The outdoor unit will not operate for 3 minutes after the
power is turned ON and after operation is stopped.)
(2) All the indicator lamps blink while the test run is in progress.
(3) Temperature control is not possible during the test run.
(4) If correct operation is not possible, the trouble will be
indicated by the indicator lamps.
Refer to "Table of Self-Diagnostic Functions and Corrections
(Type K1)" and correct the problem.
(5) After the test is completed, change the control unit switch
from "TEST" → "ON".
Confirm that the indicator lamps have stopped blinking. (A function is included which cancels the test run after
a 60-minute timer has elapsed, in order to prevent continuous test run operation.)
N OT E
This mode places a large load on the devices. Use it only for performing test runs.
A test run is not possible if the power is turned ON with the switch in the TEST position.
After the power has been turned ON, change the switch once to ON or OFF, then switch it back to the TEST
position.
Precautions
Request that the customer be present when the test run is performed.
At this time, explain the Operating Instructions and have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the customer.
Check that the 220 – 240 V AC wiring is not connected to the inter-unit control wiring connector terminal.
* If 220 – 240 V AC is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5 A for both indoor
and outdoor units) will blow in order to protect the PCB.
Correct the wiring connections, then disconnect the 2P connectors (indoor: blue) (outdoor: blue, serial 1)
that are connected to the PCB, and replace them with 2P connectors (indoor: brown) (outdoor: brown, serial 2).
If operation is still not possible after changing the brown connectors, cut off the jumper (outdoor unit : JP007)
or the varistor (indoor unit) on the PCB. (Be sure to turn the power OFF before performing this work.)
Outdoor unit control PCB
HIC
Temperature
sensor
Up side
C2(CN020,WHT)
MOV(CN025,WHT)
63PH(CN004,RED)
Bottom
side
AUTO ADD(CN041)
System address
Rotary switch(S002)
TERMINAL (CN003)
JP007
System address
DIP switch (S003)
RC-P(CN032,RED)
LED1
LED2
PUMP DOWN(CN042)
EEPROM(IC006)
C1(CN021,BLK)
TO(CN022,WHT)
TD,TS(CN023,WHT)
SILENT MODE(CN028,WHT)
RC-P(CN034,RED)
FAN(CN030,WHT)
ROM(CN012,WHT)
OC(CN013,BLU)
EMG(CN014,BRN)
20S(CN09,WHT)
FUSE(30A,F003)
1-302
Indoor control unit switch
ON
OFF
TEST
Indicator lamps
OPERATION
Indoor unit control PCB
2 HP
Varistor (black)
VA002
2P connector (brown)
2P connector (blue)
3 HP
CHK (2P plug)
TIMER
STANDBY
Fuse (0.5A)
CHK (2P plug)
TEST
SW103
ON
OFF
Fuse (0.5A)
2P connector (blue)
2P connector (brown)
ON
SW103
OFF
TEST
Varistor (black)
VA002