Danfoss VLT AAF006 Operating Instructions Manual page 75

Active filter
Hide thumbs Also See for VLT AAF006:
Table of Contents

Advertisement

RS485 Installation and Set-...
Text block
The text block is used to read or write texts via the data block.
STX
LGE
Illustration 7.7 Text Block
7.3.7 The PKE Field
The PKE field contains 2 sub-fields:
Parameter command and response AK
Parameter number PNU
7
7
AK
15 14 13 12 11 10 9
Illustration 7.8
Bits 12–15 transfer parameter commands from master to
slave and return processed slave responses to the master.
Parameter commands master⇒slave
Bit no.
15
14
13
0
0
0
0
0
0
0
0
1
0
0
1
1
1
0
1
1
1
1
1
1
Table 7.4 Parameter Commands from Master to Slave
72
Operating Instructions
ADR
PKE
IND
PKE
IND
PWE
high
PNU
8
7
6
5
4
3
2
1
Parameter command
12
0
No command
1
Read parameter value
0
Write parameter value in RAM (word)
1
Write parameter value in RAM (double
word)
1
Write parameter value in RAM and
EEprom (double word)
0
Write parameter value in RAM and
EEprom (word)
1
Read/write text
Danfoss A/S © 09/2014 All rights reserved.
Ch1
Ch2
Chn
Response slave⇒master
Bit no.
15
14
0
0
0
0
0
0
0
1
PWE
low
1
1
Table 7.5 Parameter Response from Slave to Master
If the command cannot be performed, the slave sends this
response:
0
0111 Command cannot be performed
- and issues the following fault report in the parameter
value (PWE):
PWE low
(hex)
0
1
2
3
4
5
11
82
83
Table 7.6 Fault Definitions
7.3.8 Parameter Number (PNU)
Bits 0–1 transfer parameter numbers. The function of the
relevant parameter is defined in the parameter description
in the Programming Guide.
PCD1
PCD2
Response
13
12
0
0
No response
0
1
Parameter value transferred (word)
1
0
Parameter value transferred (double
word)
1
1
Command cannot be performed
1
1
Text transferred
Fault report
The parameter number used does not exist.
There is no write access to the defined parameter.
Data value exceeds the parameter limits.
The sub index used does not exist.
The parameter is not the array type.
The data type does not match the defined
parameter.
Data change in the defined parameter is not
possible in the unit's present mode. Certain
parameters can only be changed when the motor
is turned off.
There is no bus access to the defined parameter.
Data change is not possible because factory set-
up is selected.
BCC
MG90V302