AHF 005/010 Warnings Avoid filter module damage The Danfoss harmonic filter AHF 005 and 1. The filter modules are to be used only with AHF 010 contain dangerous voltages Danfoss frequency converters. The usage when connected to line voltages. Only...
AHF 005/010 Description The Danfoss harmonic filters AHF 005 and AHF 010 Legends (as used throughout this manual): are ensuring near sinusoidal line current minimising Line voltage the harmonic current emission into the mains supply. Input current of the filter...
8500 * Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 400V and assuming typical motor load (4 or 2 pole motor). VLT 5000 series is based on a max. 160 % torque application, while VLT 6000 and 8000 series are based on a max.
6500 8500 * Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 480V and assuming typical motor load. VLT 5000 series is based on a 160 % torque application, while VLT 6000 and 8000 series are based on 110% torque application.
Overvoltage category III according to VDE 0110 Packaging DIN 55468 for transport packaging materials Type of protection IP 20 Approvals CE: Low-Voltage Directive; UL; C-tick *climatic conditions according to class 3K3 (EN 50178 Part 6.1) MG.80.B2.02 - VLT is a registered Danfoss trademark...
119 Kg (262 lbs) 289 A 135 Kg (298 lbs) 289 A 145 Kg (320 lbs) 324 A 180 Kg (397 lbs) AHF 005, 380 – 415 V AC, 50Hz AHF 005, 440 – 480 V AC, 60Hz Frame Weight Frame Weight AHF,N...
- The supply terminals L1, L2 and filter module terminals X2.1, X2.2 and X2.3. L3 of several frequency converters must be connected to the filter module terminals X2.1, X2.2 and X2.3. MG.80.B2.02 - VLT is a registered Danfoss trademark...
Over temperature contactor The Danfoss harmonic filter AHF 005 and AHF 010 is equipped with a galvanic isolated contactor that is closed under normal operating conditions and open if the filter is overheated. This contactor can be used for preventing damages to the filter caused by over temperature as shown in the following example.
Allowed Indirectly grounded star point Allowed Isolated star point Allowed The filter module has been designed completely symmetrically for three phase operation and without reference to the star point or protective earth. MG.80.B2.02 - VLT is a registered Danfoss trademark...
1. Switch on mains supply : - The filter module is ready for operation at once. 2. Check the readiness of the frequency converter: - Proceed in accordance with the operating instructions of the frequency converter. MG.80.B2.02 - VLT is a registered Danfoss trademark...
The filter modules have to be protected from inadmissible stress. In particular during transport and handling no components are allowed to be bend MG.80.B2.02 - VLT is a registered Danfoss trademark...
During operation, all covers and doors must be closed. 7. Maintenance and service The manufacturer’s documentation must be observed. This safety information must be kept! The product-specific safety and application notes in these Operating Instructions must also be observed! MG.80.B2.02 - VLT is a registered Danfoss trademark...
Page 18
XREF__BC NOT LOADED ON RIP Harmonic Filter AHF 005/010 Instruction Manual REV. 2003-06-18 175R0932 MG80B202 *MG80B202*...