Applications and Basic Prog...
14-22 Operation Mode
Option:
Function:
12
13
18
12 13
18
39 42
50
Illustration 6.8 Terminal Connections
[2]
Initiali-
Select [2] Initialisation to reset all parameter
sation
values to default settings, except for
parameter 15-03 Power Up's,
parameter 15-04 Over Temp's, and
parameter 15-05 Over Volt's. The unit resets
during the next power-up.
Parameter 14-22 Operation Mode also reverts to
the default setting [0] Normal operation.
[3]
Boot
mode
14-29 Service Code
Range:
0
[-2147483647 - 2147483647]
*
14-50 RFI Filter
Option: Function:
[0]
Off Select [0] Off only if the unit is fed by an isolated
mains source (IT mains).
In this mode, the internal RFI filter capacitors between
chassis and the mains RFI filter circuit are cut-out to
reduce the ground capacity currents.
[1]
On
Select [1] On to ensure that the unit complies with
*
EMC standards.
14-54 Bus Partner
Range:
1
[0 - 126 ]
*
MG90V302
Operating Instructions
19
27
29
32
33 20
37
FC 302
19
27
32
33
20
FC 301
53
54
55
FC 301 &
FC 302
Function:
For internal service only.
Function:
Danfoss A/S © 09/2014 All rights reserved.
6
6
51