  • Page 1: Table Of Contents

    AHF 005/010 Operating Instructions Contents Contents 1 Safety Warnings Symbols Used in This Manual Operator's Safety Avoid Filter Module Damage 2 Ordering Numbers Description Ordering Numbers, 380 - 415V, 50Hz Ordering Numbers, 380 - 415V, 60Hz Ordering Numbers, 440 - 480V, 60Hz...
  • Page 2 Contents AHF 005/010 Operating Instructions Index ® MG.80.C2.02 - VLT is a registered Danfoss trademark...
  • Page 3: Safety

    1.1.1 Warnings The Danfoss harmonic filter AHF 005 and AHF 010 contain dangerous voltages when connected to mains voltages. Only a competent electrician should carry out the electrical installation. Improper installation of the filter or the connected frequency converter may cause equipment failure, serious injury or death.
  • Page 4: Avoid Filter Module Damage

    AHF 005/010 Operating Instructions 1.1.4 Avoid Filter Module Damage The filter modules may only be used with Danfoss frequency converters. Do not use the drive system (frequency converter, motor load and filter) if the equipment has been damaged. Modifications of the filters are not allowed.
  • Page 5: Ordering Numbers

    The Danfoss AHF 005 and AHF 010 are advanced harmonic filters not to be compared with traditional harmonic trap filters. The Danfoss harmonic filters have been specially designed to match all the Danfoss frequency converters. The filters AHF 010 and AHF 005 are available in five voltage versions.
  • Page 6: Ordering Numbers, 380 - 415V, 50Hz

    Table 2.2: AHF 005 and AHF 010, 380V - 415V, 50Hz ⋆ Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 400V and assuming typical motor load (4 or 2 pole motor). (FC 300 is based on an 160% torque application, while FC 100 and FC 200 Series are based on 110% torque application.) The pre-calculated filter current may be different than the input current ratings of FC 100, FC 200 and FC 300 series as stated in the respective operating instructions, as these numbers are based on different operating conditions.
  • Page 7: Ordering Numbers, 440 - 480V, 60Hz

    Table 2.4: AHF005 and AHF010, 440 - 480V, 60Hz ⋆ Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 480V and assuming typical motor load. FC 300 is based on an 160% torque application, while FC 100 and FC 200 series are based on 110% torque application.
  • Page 8: Ordering Numbers, 690V, 50Hz

    AHF 005/010 Operating Instructions ⋆ Please note that the matching of the typical Danfoss frequency converter and filter is pre-calculated based on 500V and assuming typical motor load. FC 300 is based on an 160% torque application, while FC 100 and FC 200 series are based on 110% torque application.
  • Page 9: Specifications

    AHF 005/010 Operating Instructions 3 Specifications 3 Specifications 3.1.1 General Technical Data AHF 0xx AHF 0xx AHF 0xx AHF 0xx AHF 0xx 380 ≤ U ≤ 415 380 ≤ U ≤ 415 440 ≤ U ≤ 480 Nominal supply 500 V...
  • Page 10: Dimensions/Weight

    3.1.3 Dimensions/Weight The AHF modules are available in seven frame sizes (size B to H). For dimensions see the drawings on the following pages AHF 005, 380 – 415 V AC, 50Hz AHF 010, 380– 415 V AC, 50Hz Frame size...
  • Page 11: Dimension Diagrams

    AHF 005/010 Operating Instructions 3 Specifications AHF 005, 690V AC, 50Hz AHF 010, 690 V AC, 50Hz Frame size Weight Frame size Weight AHF,N AHF,N 43 A 85 kg (187 lbs) 43 A 65 kg (143 lbs) 72 A 100 kg (220 lbs)
  • Page 12 3 Specifications AHF 005/010 Operating Instructions Illustration 3.3: Frame size D Illustration 3.4: Frame size E ® MG.80.C2.02 - VLT is a registered Danfoss trademark...
  • Page 13 AHF 005/010 Operating Instructions 3 Specifications Illustration 3.5: Frame size F Illustration 3.6: Frame size G ® MG.80.C2.02 - VLT is a registered Danfoss trademark...
  • Page 14 3 Specifications AHF 005/010 Operating Instructions Illustration 3.7: Frame size H Illustration 3.8: Detailed drawing of mounting feet. Please allow an additional 30 mm of depth of the filter for the mounting feet. Filter frame E-H should only be transported upright, i.e. by using the lifting hooks.
  • Page 15: Installation

    AHF 005/010 Operating Instructions 4 Installation 4 Installation 4.1.1 Mechanical Installation The encapsulation of the filters have an IP 20 rating. The filters can be mounted side by side with 60 mm (2,36 inches) clearance. To other components and to the cabinet walls keep a horizontal clearance of at least 70 mm (2,76 inches) and a vertical clearance of at least 150 mm (5,91 inches).
  • Page 16: Ventilation

    5306 W Table 4.1: Max. heat losses at full load under-voltage. If other heat sources (e.g. Danfoss frequency converters) are installed in an enclosure with the harmonic filter AHF 0xx, this heat generation must also be considered when calculating required airflow If the cooling air is polluted (dust, dirt swirl, grease, aggressive gas) the function of the filter module may be impeded.
  • Page 17 A maximum cable lenght of 2 meters are allowed between filter and contactor. * Power wiring used for connection of the filter AHF 005 and AHF 010 in enclosure size E, F and G must be terminated with cable lugs that can be attached to the input and output bus bars terminals.
  • Page 18: Capacitor Disconnect

    4.1.4 Capacitor Disconnect The power factor of the harmonic filter AHF 005/010 is decreasing with decreasing load. At zero load the Power Factor becomes zero and the capacitors produce approximately 30% leading current compared to the rated current of the filter. The reactive current generated by the filter at partial load is normally not of any concern, mainly because of the small current compared to the system capacity (max.
  • Page 19 AHF 005/010 Operating Instructions 4 Installation 380 - 415V 380 - 415V 440 - 480V 500 - 525V 690V 50Hz 60Hz 60Hz 50Hz 50Hz Contactor Rating Contactor Rating Contactor Rating Contactor Rating Contactor Rating AHF,N kVAr kVAr kVAr kVAr kVAr...
  • Page 20 4 Installation AHF 005/010 Operating Instructions Illustration 4.3: Connection diagram of filter and frequency converter assembly. AB terminals are not Protected Extra Low Voltage (PELV). ® MG.80.C2.02 - VLT is a registered Danfoss trademark...
  • Page 21: Fuses

    The filter must be protected against short-circuit and overload to avoid electrical or fire hazard and to protect cables and filter from overheating. Danfoss recommends using fuses mentioned below to protect service personnel and equipment in case of an internal failure in the filter.
  • Page 22: Over Temperature Switch

    See the section on fuses in the 4.1.6 Over Temperature Switch The Danfoss harmonic filters AHF 005 and AHF 010 are equipped with a galvanic isolated thermal switch (not PELV), that is closed under normal operating conditions and open if the filter is overheated.
  • Page 23: Operation On Different Mains Type

    AHF 005/010 Operating Instructions 4 Installation The maximum rating of the over temperature contactor is 250V AC and 10A. The switch must be used to prevent damage to the filter caused by over temperature. 4.1.7 Operation on Different Mains Type...
  • Page 24 4 Installation AHF 005/010 Operating Instructions Illustration 4.4: Typical panel installation Panel Mains supply wire Motor wiring Control wiring Wiring between harmonic filter and frequency converter Mains supply wire of filter module Mounting plate (common star point) Potential equalisation Filter AHF 0xx...
  • Page 25: Commissioning

    AHF 005/010 Operating Instructions 5 Commissioning 5 Commissioning Prior to initial switch-on of the filter check the wiring for completeness, short-circuit and earth fault. If the wiring is not correct, a non-intended operation of controller and/or filter is possible. First powering up Switch on mains supply : - The filter is ready for operation at once.
  • Page 26 6 Appendix: Safety and Application Notes AHF 005/010 Operating Instructions ® MG.80.C2.02 - VLT is a registered Danfoss trademark...
  • Page 27: Appendix: Safety And Application Notes

    AHF 005/010 Operating Instructions 6 Appendix: Safety and Application Notes 6 Appendix: Safety and Application Notes 6.1.1 General During operation, filter module units may have, according to their type of protection, live, bare, in some cases also movable or rotating parts as well as internal hot surfaces.
  • Page 28: Electrical Installation

    6 Appendix: Safety and Application Notes AHF 005/010 Operating Instructions 6.1.5 Electrical Installation When working on live filters, the valid national regulations for the prevention of accidents (e.g. VBG 4) must be observed. Before any installation or connection works, the plant has to be switched off and to be secured properly.
  • Page 29 AHF 005/010 Operating Instructions Index Index Application As Directed Avoid Filter Module Damage Cable Lengths And Cross Sections Calculation Of The Exact Filter Size Needed Capacitor Disconnect Capacitor Disconnect (copper) Capacitor Disconnect Ratings. Commissioning Description Dimension Diagrams Dimensions/weight Electrical Installation...
  • Page 30 Index AHF 005/010 Operating Instructions Transport And Storage Typical Installation In A Panel Or Other Enclosures Ventilation Warnings ® MG.80.C2.02 - VLT is a registered Danfoss trademark...