Switch Installation
Procedure
Step 1
Use a wire-stripping tool to remove approximately 0.5 inch (12.7 mm) ± 0.02 inch (0.5 mm) of the covering
from the end of the grounding wire.
Step 2
Insert the stripped end of the grounding wire into the open end of the grounding lug.
Step 3
Crimp the grounding wire in the barrel of the grounding lug. Verify that the ground wire is securely attached
to the ground lug.
Step 4
Place the grounding wire lug against the grounding pad, making sure that there is solid metal-to-metal contact.
Step 5
Secure the grounding lug to the chassis with two grounding screws. Ensure that the grounding lug and the
grounding wire will not interfere with other switch hardware or rack equipment.
Step 6
Connect the other end of the grounding wire to an appropriate grounding point at your site or to the rack.

Installing the Power Cord Retainer

The power cord retainer (PWR-CLP=) is optionally supplied as part of accessory kit with the 5RU 19" rack
mount chassis (CDB-MNT-RACK5-C14) and flexible mount with IEC C14 power junction box
(CDB-MNT-FLEX-C14).