User Response
If the specified sensor is Planar 3.3V or Planar 5V, (Trained technician only) replace the system board.
If the specified sensor is Planar 12V, complete the following steps until the problem is solved:
1. Check power supply n LED.
2. Remove the failing power supply.
3. (Trained technician only) Replace the system board. (n = power supply number)
80010b01-0701ffff : Numeric sensor [NumericSensorElementName] going high (upper
non-recoverable) has asserted. (Ambient Temp)
This message is for the use case when an implementation has detected an Upper Non-recoverable
sensor going high has asserted.
May also be shown as 80010b010701ffff or 0x80010b010701ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0498
User Response
1. Make sure there is a node filler correctly installed for the empty node slot.
2. Make sure the air baffles are placed and correctly installed; and make sure the node cover
is installed and completely closed.
3. Make sure the fans are operating, and there are no obstructions to the airflow (both front and
rear of the server).
4. Reduce the Ambient temperature. The system must be operating within the specifications. (see
Features and specifications for more information)
80010b01-0702ffff : Numeric sensor [NumericSensorElementName] going high (upper
non-recoverable) has asserted. (DIMM AB Temp)
This message is for the use case when an implementation has detected an Upper Non-recoverable
sensor going high has asserted.
May also be shown as 80010b010702ffff or 0x80010b010702ffff
Appendix A. Integrated Management Module II (IMM2) error messages
265