Hitachi SJ700D-004L Instruction Manual page 222

Sj700d-3 series
Hide thumbs Also See for SJ700D-004L:
Table of Contents

Advertisement

Chapter 4
Register No.
Function name
1301h
Selection of restart mode
Allowable under-voltage power
1302h
failure time
Retry wait time before motor
1303h
restart
Instantaneous power
1304h
failure/under-voltage trip alarm
enable
Number of restarts on power
1305h
failure/under-voltage trip events
1306h
Input phase loss detection enable
1307h
Restart frequency threshold
1308h
1309h
Selection of retry after tripping
Selection of retry count after
130Ah
undervoltage
Selection of retry count after
130Bh
overvoltage or overcurrent
130Ch
Retry wait time after tripping
Electronic thermal setting
130Dh
(calculated within the inverter from
current output)
130Eh
Electronic thermal characteristic
130Fh
(Reserved)
Free setting, electronic thermal
1310h
frequency (1)
Free setting, electronic thermal
1311h
current (1)
Free setting, electronic thermal
1312h
frequency (2)
Free setting, electronic thermal
1313h
current (2)
Free setting, electronic thermal
1314h
frequency (3)
Free setting, electronic thermal
1315h
current (3)
Overload restriction operation
1316h
mode
1317h
Overload restriction setting
Deceleration rate at overload
1318h
restriction
Overload restriction operation
1319h
mode (2)
131Ah
Overload restriction setting (2)
Deceleration rate at overload
131Bh
restriction (2)
131Ch
Overcurrent suppression enable
Active frequency matching scan
131Dh
start frequency
Active frequency matching,
131Eh
scan-time constant
Active frequency matching, restart
131Fh
frequency select
1320h
Software lock mode selection
1322h
(Reserved)
1323h
Run/power-on warning time
1324h
(Note) <>indicate the setting range of 75 to 150kW
Function code
R/W
Monitoring and setting items Data resolution
0 (tripping), 1 (starting with 0 Hz), 2 (starting with
matching frequency), 3 (tripping after deceleration and
b001
R/W
stopping with matching frequency), 4 (restarting with
active matching frequency)
b002
R/W 3 to 250
b003
R/W 3 to 1000
0 (disabling), 1 (enabling), 2 (disabling during stopping
b004
R/W
and decelerating to stop)
b005
R/W 0 (16 times), 1 (unlimited)
b006
R/W 0 (disabling), 1 (enabling)
b007 (high)
R/W
0 to 40000
b007 (low)
R/W
0 (tripping), 1 (starting with 0 Hz), 2 (starting with
matching frequency), 3 (tripping after deceleration and
b008
R/W
stopping with matching frequency), 4 (restarting with
active matching frequency)
b009
R/W 0 (16 times), 1 (unlimited)
b010
R/W 1 to 3
b011
R/W 3 to 1000
b012
R/W 200 to 2000 <200 to 1800>(CT),200 to 1500(VT)
0 (reduced-torque characteristic), 1 (constant-torque
b013
R/W
characteristic), 2 (free setting)
-
-
Inaccessible
b015
R/W 0 to 400
b016
R/W 0 to Rated current
b017
R/W 0 to 400
b018
R/W 0 to Rated current
b019
R/W 0 to 400
b020
R/W 0 to Rated current
0 (disabling), 1 (enabling during acceleration and
constant-speed operation), 2 (enabling during
b021
R/W
constant-speed operation), 3 (enabling during
acceleration and constant-speed operation [speed
increase at regeneration])
b022
R/W 200 to 2000 <200 to 1800>(CT),200 to 1500(VT)
b023
R/W 10 to 3000
0 (disabling), 1 (enabling during acceleration and
constant-speed operation), 2 (enabling during
b024
R/W
constant-speed operation), 3 (enabling during
acceleration and constant-speed operation [speed
increase at regeneration])
b025
R/W 200 to 2000 <200 to 1800>(CT),200 to 1500(VT)
b026
R/W 10 to 3000
b027
R/W 0 (disabling), 1 (enabling)
b028
R/W 200 to 2000
b029
R/W 10 to 3000
0 (frequency at the last shutoff), 1 (maximum
b030
R/W
frequency), 2 (set frequency)
0 (disabling change of data other than "b031" when SFT
is on), 1 (disabling change of data other than "b031"
and frequency settings when SFT is on), 2 (disabling
b031
R/W
change of data other than "b031"), 3 (disabling change
of data other than "b031" and frequency settings), 10
(enabling data changes during operation)
-
-
Inaccessible
b034 (high)
R/W
0 to 65535
b034 (low)
R/W
4-151
Explanation of Functions
Data
resolution
-
0.1 [sec.]
0.1 [sec.]
-
-
-
0.01 [Hz]
-
-
1 [time]
0.1 [sec.]
0.1 [%]
-
-
1 [Hz]
0.1 [A]
1 [Hz]
0.1 [A]
1 [Hz]
0.1 [A]
-
0.1 [%]
sec.
0.01 [
]
-
0.1 [%]
0.01 [
sec.
]
-
0.1 [%]
sec.
0.01 [
]
-
-
-
1 [10h]

Advertisement

Table of Contents
loading

Table of Contents