Hitachi SJ700D-004L Instruction Manual page 193

Sj700d-3 series
Hide thumbs Also See for SJ700D-004L:
Table of Contents

Advertisement

Chapter 4
(vi) 05 command: This command reads the trip history data from the inverter.
- Transmission frame
Frame format
STX
Station No.
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
Command
Command to be transmitted
BCC
Block check code
CR
Control code (Carriage Return)
- Response frame
Frame format
STX
Station No.
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
Data
Data monitored at tripping
BCC
Block check code
CR
Control code (Carriage Return)
Note 11: The inverter stores the data (trip history) on the last six times of tripping, together with the total trip count
(8 bytes).
Total trip count
Trip 1 data
Monitoring item
Trip factor
Inverter status A
Inverter status B
Inverter status C
Output frequency
Cumulative running time
Output current
DC voltage
Cumulative power-on time
Command
BCC
Description
Data
BCC
Description
・・・・・・
Unit
Magnification
-
-
-
-
-
-
-
-
Hz
×10
hour
×1
A
×10
V
×10
hour
×1
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32
2 bytes
05
XOR of the items from "Station No." to "Data." See
2 bytes
Item (3) of this section.
1 byte
CR (0x0D)
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32
440 bytes
See Note 9.
XOR of the items from "Station No." to "Data." See
2 bytes
Item (3) of this section.
1 byte
CR (0x0D)
Trip 6 data
Data size
8 bytes
Factor code
8 bytes
04 command
8 bytes
See Note 7.
8 bytes
8 bytes
Decimal ASCII code
8 bytes
Decimal ASCII code
8 bytes
Decimal ASCII code
8 bytes
Decimal ASCII code
8 bytes
Decimal ASCII code
4-122
Explanation of Functions
Setting
Setting
Remarks

Advertisement

Table of Contents
loading

Table of Contents