Chapter 3
You can operate the inverter in different ways, depending on how to input the operation and frequency-setting
commands as described below.
This section describes the features of operating methods and the items required for operation.
(1) Entering operation and frequency-setting commands from the digital operator
This operating method allows you to operate the inverter through key operations on the standard digital operator
mounted in the inverter or an optional digital operator.
When operating the inverter with a digital operator alone, you need not wire the control circuit terminals.
(Items required for operation)
*) Optional digital operator (not required when you use the standard digital operator)
(2) Entering operation and frequency-setting commands via control circuit terminals
This operating method allows you to operate the inverter via the input of operation signals from external devices
(e.g., frequency-setting circuit and start switch) to control circuit terminals. The inverter starts operation when the
input power supply is turned on and then an operation command signal (FW or RV) is turned on. You can select the
frequency-setting method (setting by voltage specification or current specification) through the input to a control
circuit terminal according to your system. For details, see Item (2), "Explanation of control circuit terminals," in
Section 2.2.1. (Items required for operation)
1) Operation command input device: External switch or relay
2) Frequency-setting command input device: External device to input signals (0 to 10 VDC, -10 to +10 VDC, or 4 to 20
mA)
Frequency-setting command input
device (control)
(3) Entering operation and frequency-setting commands; both from a digital operator and via control circuit terminals
This operating method allows you to arbitrarily select the digital operator or control circuit terminals as the means
to input operation commands and frequency-setting commands. (Items required for operation)
1) See the items required for the above two operating methods.
(4) Operation by Easy sequence function (Drive programming function)
The inverter can be operated by downloading the user's program made with the dedicated PC software,
ProDriveNext. Please refer to "Easy sequence function" for details.
(5) Operation via communication
The inverter can be operated by an external communication device via Modbus-RTU or ASCII protocol (Hitachi
protocol) through the TM2 terminal on the control terminal l board. Please refer to "Communication function" for
details.
Digital operator
H
Control circuit
terminal block
FW CM1
O L
Operation command input device
(switch)
3-2
Operation