Chapter 4
(ii) List of registers (frequency settings and trip monitoring)
Register
Function name
No.
0001h
Frequency source setting
0002h
0003h Inverter status A
0004h Inverter status B
0005h Inverter status C
0006h PID feedback
0007h
to
(Reserved)
0010h
0011h Trip Counter
0012h Trip monitoring 1 (factor)
0013h Trip monitoring 1 (inverter status)
0014h Trip monitoring 1 (frequency) (high)
0015h Trip monitoring 1 (frequency (low)
0016h Trip monitoring 1 (current)
0017h Trip monitoring 1 (voltage)
0018h Trip monitoring 1 (running time) (high)
0019h Trip monitoring 1 (running time) (low)
001Ah Trip monitoring 1 (power-on time) (high)
001Bh Trip monitoring 1 (power-on time) (low)
001Ch Trip monitoring 2 (factor)
001Dh Trip monitoring 2 (inverter status)
001Eh Trip monitoring 2 (frequency) (high)
001Fh Trip monitoring 2 (frequency (low)
0020h Trip monitoring 2 (current)
0021h Trip monitoring 2 (voltage)
0022h Trip monitoring 2 (running time) (high)
0023h Trip monitoring 2 (running time) (low)
0024h Trip monitoring 2 (power-on time) (high)
0025h Trip monitoring 2 (power-on time) (low)
0026h Trip monitoring 3 (factor)
0027h
Trip monitoring 3 (inverter status)
0028h Trip monitoring 3 (frequency) (high)
0029h Trip monitoring 3 (frequency (low)
002Ah Trip monitoring 3 (current)
002Bh Trip monitoring 3 (voltage)
002Ch Trip monitoring 3 (running time) (high)
002Dh Trip monitoring 3 (running time) (low)
002Eh Trip monitoring 3 (power-on time) (high)
002Fh
Trip monitoring 3 (power-on time) (low)
0030h Trip monitoring 4 (factor)
0031h Trip monitoring 4 (inverter status)
0032h Trip monitoring 4 (frequency) (high)
0033h Trip monitoring 4 (frequency (low)
0034h Trip monitoring 4 (current)
0035h Trip monitoring 4 (voltage)
0036h Trip monitoring 4 (running time) (high)
0037h Trip monitoring 4 (running time) (low)
0038h Trip monitoring 4 (power-on time) (high)
0039h Trip monitoring 4 (power-on time) (low)
Function code R/W
F001 (high)
R/W 0 to 40000 (valid when A001 = 03)
F001 (low)
R/W
0: Initial status, 1: Waiting for Vdc establishment, 2:
Stopping, 3: Running, 4: Free-run stop (FRS), 5:
-
R
Jogging, 6: DC braking, 7: Frequency being input, 8:
Retrying operation, 9: Undervoltage (UV),
-
R
0: Stopping, 1: Running, 2: Tripping
0: ---, 1: Stopping, 2: Decelerating, 3: Constant-speed
operation, 4: Accelerating, 5: Forward rotation, 6:
Reverse rotation, 7: Switching from forward rotation
-
R
to reverse rotation, 8: Switching from reverse
rotation to forward rotation, 9: Starting forward
rotation, 10: Starting reverse rotation
-
R/W 0 to 10000
-
R
Inaccessible
d080
R
0 to 65530
See the list of inverter trip factors below
See the list of inverter trip factors below
0 to 40000
Output current at tripping
d081
R
DC input voltage at tripping
Cumulative running time at tripping
Cumulative power-on time at tripping
See the list of inverter trip factors below
See the list of inverter trip factors below
0 to 40000
Output current at tripping
d082
R
DC input voltage at tripping
Cumulative running time at tripping
Cumulative power-on time at tripping
See the list of inverter trip factors below
See the list of inverter trip factors below
0 to 40000
Output current at tripping
d083
R
DC input voltage at tripping
Cumulative running time at tripping
Cumulative power-on time at tripping
See the list of inverter trip factors below
See the list of inverter trip factors below
0 to 40000
Output current at tripping
d084
R
DC input voltage at tripping
Cumulative running time at tripping
Cumulative power-on time at tripping
4-143
Explanation of Functions
Monitoring and setting items
Data
resolution
0.01 [Hz]
-
-
-
0.01 [%]
-
1 [time]
-
-
0.01 [Hz]
0.1 [A]
1 [V]
1[h]
1[h]
-
-
0.01 [Hz]
0.1 [A]
1 [V]
1[h]
1[h]
-
-
0.01 [Hz]
0.1 [A]
1 [V]
1[h]
1[h]
-
-
0.01 [Hz]
0.1 [A]
1 [V]
1[h]
1[h]