Chapter 4
4.1.5 Intelligent input terminal status
When the intelligent input terminal status function (d005) is selected, the
inverter displays the states of the inputs to the intelligent input terminals.
The internal CPU of the inverter checks each intelligent input for significance, and the inverter displays active inputs
as those in the ON state. (*1)
Intelligent input terminal status is independent of the a/b contact selection for the intelligent input terminals.
(Example)
FW terminal and intelligent input terminals [7], [2], and [1]: ON
Intelligent input terminals [8], [6], [5], [4], and [3]: OFF
Intelligent input terminals
(*1)When input terminal response time is set, terminal recognition is delayed. (refer 4.2.79)
4.1.6 Intelligent output terminal status
When the intelligent output terminal status function (d006) is selected, the
inverter displays the states of the outputs from the intelligent output terminals.
This function does not monitor the states of the control circuit terminals but monitors those of the outputs from the
internal CPU.
Intelligent input terminal status is independent of the a/b contact selection for the intelligent input terminals.
(Example)
Intelligent output terminals [12] and [11]: ON
Alarm relay terminal AL and intelligent output terminals [15] to [13]: OFF
Intelligent input terminals
4.1.7 Scaled output frequency monitoring
When the scaled output frequency monitoring (d007) is selected, the inverter
displays the gain data converted from the output frequency with the
frequency scaling conversion factor (b086).
Use this function, for example, to change the unit of a value (e.g., motor speed) on display.
Value displayed by function "d007" = "output frequency monitor(d001)" x "frequency scaling conversion factor (b086)"
The frequency scaling conversion factor (b086) can be set within the range 0.1 to 99.9 in steps of 0.1.
(Example) Displaying the speed of a 4-pole motor
-1
Speed N (min
) = (120 x f [Hz])/pole = f (Hz) x 30
As the result of the above calculation with the factor (b086) set to 30.0, the inverter displays "1800" (60 x 30.0)
when the output frequency is 60 Hz.
(Display)
0.00 to 99.99 in steps of 0.01
100.0 to 999.9 in steps of 0.1
1000. to 9999. in steps of 1
1000 to 3996 in units of 10
Note: When you have selected the digital operator as the device to input frequency-setting commands, you can
change the output frequency setting by using the △ and/or ▽ key (only while the inverter is operating the
motor).
- The change in output frequency made in this mode can be reflected in the frequency setting (function "F001").
Press the STR key to write the new frequency over the currently selected frequency setting. (The precision of
the storable frequency data depends on the frequency setting.)
- You cannot change the output frequency while the PID function is enabled or the inverter is not operating the
motor.
ON
FW
OFF
8
7
6
5
(OFF)
(ON)
(OFF)
(OFF)
(OFF)
AL
15
(OFF)
(OFF)
(OFF)
Explanation of Functions
Display
ON
OFF
4
3
2
1
(OFF)
(ON)
(ON)
d006: Intelligent output terminal status
Display
ON
OFF
12
14
13
11
(OFF)
(ON)
(ON)
d007: Scaled output frequency monitoring
b086: Frequency scaling conversion factor
4-2
Related code
d005: Intelligent input terminal status
: The segment is on, indicating
the ON state.
: The segment is off, indicating
the OFF state.
Related code
: The segment is on, indicating
the ON state.
: The segment is off, indicating
the OFF state.
Related code