YOKOGAWA WT500 User Manual page 308

Power analyzer
Hide thumbs Also See for WT500:
Table of Contents

Advertisement

tem
Effective input range
Maximum display
Minimum display
Lower limit of measurement
frequency
Line filter influence
Conditions for detecting
lead and lag
(D/G, for lead and lag, of
f
*
phase angle
; sign s
when
computing reactive power
Σ
Q
)
Temperature coefficient
One year accuracy
Accuracy when the crest
factor is set to 6
IM 760201-01E
Specifications
0 to ±110% of the measurement range for Udc and Idc.
1 to 110% of the measurement range for Urms and Irms (2 to 220% when the crest factor is set to 6).
10 to 110% of the measurement range for Umn and Imn.
10 to 110% of the measurement range for Urmn and Irmn.
10 to 110% of the measurement range for Uac and Iac.
However, the synchronization source signal level must meet the frequency measurement input
signal level (see section 14.5 for details).
* 100% for the maximum voltage range.
140% of the rated voltage or current range.
As low as 0.5% of the measurement range for Urms, Uac, Irms, and Iac (1.0% when the crest factor
is set to 6). As low as 2% of the measurement range for Umn, Urmn, Imn, and Irmn (4% when the
crest factor is set to 6).
Values lower than these figures are fixed at zero. The integrated current q is dependent on the
current value.
Data update interval
100 ms 200 ms 500 ms 1 s
Lower limit of
25 Hz
measurement frequency
When the cutoff frequency is 500 Hz
45 to 66 Hz: Add 0.2% of reading. Less than 45 Hz: Add 0.5% of reading.
When the cutoff frequency is 5.5 kHz
66 Hz or less: Add 0.2% of reading. 66 to 500 Hz: Add 0.5% of reading.
Lead and lag are detected correctly when the voltage and current signals are both sine waves, the
lead and lag amplitude is greater than or equal to 50% (greater than or equal to 100% if the crest
factor is set to 6) of the measurement range, the frequency is between 20 Hz and 2 kHz, and the
phase difference is between ±5 and 175°.
* s is the sign for the lead and lag of each element. It is negative when the current leads the
voltage.
Add ±0.03% of reading/°C within the range of 5 to 18°C or 28 to 40°C.
Reading error of accuracy at 6 months × 1.5.
Same as the accuracy when the crest factor is 3 after doubling the measurement range.
*
*
*
*
2 s
12.5 Hz 5 Hz
2.5 Hz
1.25 Hz 0.5 Hz
14.5 Accuracy
*
5 s
App
Index
14-7
1
2
3
4
5
6
7
8
9
10
11
12
13
14