Specifications

1-2
Specifications
1-2-1

Performance Specifications

Item
Communications method
Communications Remote I/O
communications
Messages com-
munications
Setting, moni-
toring, and
operating Sen-
sors from Con-
figurator
Mobile Console connection
Power supply (Shared by Commu-
nication Unit and all Fiber Amplifier
Units connected to it.)
Maximum number of Sensors that
can be connected per Unit.
(See note 1.)
Applicable Fiber Amplifier Units
Applicable Slave Connectors for
Fiber Amplifier Units
Power supply cable
DeviceNet
ON/OFF data, status, and monitoring inci-
dent light levels
(Functions as DeviceNet slave.)
Explicit messages
Supported from DeviceNet Configurator
(depends on the parameter editing and
device monitoring functions of the slave).
Yes
Cannot be used at the same time as moni-
toring incident light levels from remote I/O
communications, using explicit messages
communications, or setting, monitoring, or
operating Sensors from the Configurator.
From DeviceNet communications connec-
tor
13 or 16 (depending on the mode used)
The following Fiber Amplifier Units with Connectors are supported (See note 2.):
E3X-DA6
E3X-DAB6
E3X-DAG6
E3X-DA6TW
E39-TM1
E3X-DA6-P
E3X-DA8
E3X-DAB8
E3X-DAG8
E3X-DA8TW
E3X-CN02 Cordless Slave Connector only
None
Note
1. Fiber Amplifier Units that are allocated two unit numbers must be counted
as two Units when counting the number of connected Sensors.
2. Prewired models (E3X-DA11/21/41/51-N, E3X-DAB11-N, etc.) and water-
resistant models cannot be used. Connecting these Units will disable the
power reset switch.
Specification
E3X-DRT21
Section 1-2
E3X-SRT21
E3X-CIF11
CompoBus/S
RS-422
ON/OFF data and
No
status
(Functions as Com-
poBus/S slave.)
No
Functions as
CompoWay/F
slave.
No
No
---
Cannot be used
at the same time
as CompoWay/F
message com-
munications.
From CompoBus/S
From power sup-
communications
ply cable
connector
6 or 14 (depending
16
on the setting for
maximum number
of Sensors)
E3X-CN02 Cord-
E3X-CN12 Slave
less Slave Connec-
Connector with
tor only
Cord or E3X-
CN02 Cordless
Slave Connector
None
Provided.
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

E3x-srt21E3x-cif11

Table of Contents