DeviceNet Communication Unit Part Names and Functions
Normal Status of
Indicators
Switches
Rotary Switches
DIP Switch
18
Indicator
Name
NS
Network
status
SS
Sensor
communi-
cations sta-
tus
MS
Operation is normal when the MS indicator is lit green.
NS
Operation is normal when the NS indicator is lit green
(online and communications connected).
SS
Sensors are communicating when the SS indicator is lit green.
0
X10
DeviceNet Node Address Setting
0
Set the DeviceNet node address to between 00 and 63.
X1
(64 to 99 are not used.)
1
Connected Number of Sensors Setting
Registers the number of Sensors connected. By setting the number of Sensors, errors
can be detected in the configuration.
When the DIP switch pin 3 is turned ON, however, this rotary switch is disabled. Instead,
the values set from the DeviceNet Configurator or using explicit messages are enabled.
Note
Fiber Amplifier Units (E3X-DA6TW and E3X-DA8TW) that are allocated two unit
numbers must be counted as two Units when counting the number of connected
Sensors.
Operating mode (MODE0)
Operating mode (MODE1)
Method for setting number of Sensors
Reserved for system use.
Pins 1 and 2: Operating Mode Setting
These pins set the operating mode. The data allocated in the master's IN Area
depends on the operating mode. For further details, refer to 2-5 DeviceNet
Remote I/O Communications.
Pin 1
Pin 2
(MODE0)
(MODE1)
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Color
Status
Green
Lit
DeviceNet is online and communica-
tions are connected.
Flashing DeviceNet is online and communica-
tions are not connected.
Red
Lit
A fatal DeviceNet communications
error has occurred.
Flashing A non-fatal DeviceNet communica-
tions error has occurred.
---
Not lit
DeviceNet is offline or power is OFF.
Green
Lit
Unit is communicating with Sensors.
Red
Lit
A Sensor communications error has
occurred.
---
Not lit
Sensor communications are on
standby or power is OFF
ON
1 2 3 4
Operating mode setting
Remote I/O communications one-word mode
Remote I/O communications two-word mode
Remote I/O communications two-word mode
with incident light level monitoring
Cannot be set.
Section 2-2
Meaning
Number of
Sensors
13 max.
16 max.
16 max.
---