Error Classes For I/O Devices - Siemens SIMATIC ET 200eco PN Operating Instructions Manual

Hide thumbs Also See for SIMATIC ET 200eco PN:
Table of Contents

Advertisement

Interrupt, error, and system messages
7.5 Diagnostics with STEP 7
7.5.3

Error classes for I/O devices

Error classes and remedies
The table below lists the error classes for the I/O devices.
Table 7- 6
Error classes for the IO devices digital inputs, digital outputs, analog inputs, analog outputs
Error class
Error text
00001
1
Short-circuit
B
D
00100
4
Thermal overload
B
D
00110
6
Wire break
B
D
00111
7
Violation of upper
B
D
limit
01000
8
Violation of lower
B
D
limit
01001
9
Error
B
D
10000
16
Parameterization
B
D
errors
10001
17
L1+ or 2L+ is missing 
B
D
84
Meaning
Short-circuit to M at the sensor
supply line
Output line short-circuited
Load impedance too low
I/O device is overheating
Signal line to a sensor or actuator
interrupted
Sensor or actuator failure
Load impedance too high
The value is above the overrange
Value is below the underrange
Internal I/O device error has occurred
(diagnostic message on channel 0
applies to the whole I/O device).
I/O device is incorrectly
parameterized
Supply voltages missing or too low
Load voltage supply missing or
too low
Remedy
Correct the process wiring
Check the sensor or actuator
Check the process wiring
Check the ambient temperature
Correct the process wiring
Replace the sensor or actuator
Use a sensor with lower
impedance
Use an actuator with lower load
impedance
Correct the I/O device-to-
sensor tuning
Modify measuring range by
means of parameter
assignment
Correct the I/O device-to-
sensor tuning
Modify measuring range by
means of parameter
assignment
Replacement of I/O device
Correct the parameter assignment
Check the supply voltages
Check the load voltage supply
Correct the process wiring
Operating Instructions, 06/2009, A5E01250250-04