Parameter overview analog output

Parameters for analog output 4 AO U/I 4xM12 (6ES7145-6HD00-0AB0)
Parameters
Group diagnostics
Diagnostics, missing 1L+
Diagnostics, sensor supply short circuit
Response to CPU/Master STOP
Type of output
Output range
Diagnostics, wire break at outputs
Diagnostics, short-circuit at outputs
Diagnostics, overload
Substitute value
Output range
1 to 5 V
0 to 10 V
±10 V
0 to 20 mA
4 to 20 mA
±20 mA
ET 200eco PN
Operating Instructions, 06/2009, A5E01250250-04
Range of values
Disable
Enable
Disable
Enable
Disable
Enable
Output has no current or
voltage
Keep last value
Switch to substitute values
Disabled
Voltage
Current
1 to 5 V
0 to 10 V
±10 V
0 to 20 mA
4 to 20 mA
±20 mA
Disable
Enable
Disable
Enable
Disable
Enable
Each value in the nominal
range, overrange, and
underrange
Permissible substitute value in volts or amperes
0.000 V to 5.704 V
0.000 V to 11.759 V
-11.759 V to 11.759 V
0.000 mA to 23.518 mA
0.000 mA to 22.814 mA
-23.519 mA to 23.518 mA
I/O device analog input/output
11.2 I/O device analog output
Default setting
Range of
effectiveness
Disable
Device
Disable
Device
Disable
Device
Output has no
Device
current or
voltage
Voltage
Channel
±10 V
Channel
Disable
Channel
Disable
Channel
Disable
Channel
0
Channel
173