I/O device analog input/output

11.1

I/O device analog input

11.1.1

I/O device 8 AI 4 U/I + 4 RTD/TC 8xM12

Order number
6ES7144-6KD00-0AB0
Properties
● 4 inputs for voltage and current measurement (2-wire and 4-wire transducers)
● 4 inputs for resistance (2-/3-/4-wire transducer), thermal resistor (2-/3-/4-conductor
● Input ranges:
● Dimensions 60 × 175 mm
● Diagnostics
● Permitted common-mode voltage 10 V AC
● Prioritized startup
ET 200eco PN
Operating Instructions, 06/2009, A5E01250250-04
connection system), thermocouple or ±80 mV
– ±10 V, resolution 15 bits + sign
– ±80 mV, resolution 15 bits + sign
– 0 to 10 V, resolution 15 bits
– 1 to 5 V, resolution 15 bits
– ±20 mA, resolution 15 bits + sign
– 0 to 20 mA, resolution 15 bits + sign
– 4 to 20 mA, resolution 15 bits
– 150, 300, 600, 3000 Ω, resolution 15 bits
– Ni100, Ni1000, Ni120, Ni200, Ni500, Pt100, Pt1000, Pt200, Pt500, resolution 15 bits +
sign
– E, J, K, N, resolution 15 bits + sign
– "Missing L1+" supply voltage
– "Short circuit of the sensor supply"
– "Wire break"
– "Underflow"
– "Overflow"
Note
During startup
As long as no parameters are assigned for the I/O device, the I/O device supplies the
process values 0x7fff.