Siemens SIMATIC ET 200eco PN Operating Instructions Manual page 123

Hide thumbs Also See for SIMATIC ET 200eco PN:
Table of Contents

Advertisement

Technical data
Status, interrupts, diagnostics
Interrupts
Diagnostics function
Monitoring for
Actuator selection data
Cable length, shielded
Cable length, unshielded
Output voltage
Output current
Load resistance range
Lamp load
Parallel wiring of two outputs
Control of a digital input
Switching frequency
Limiting of the inductive shutdown voltage to lamp
load
Short-circuit protection of output
* Make allowances for the maximum total current when configuring the module.
ET 200eco PN
Operating Instructions, 06/2009, A5E01250250-04
Group error/maintenance
Bus monitoring PROFINET IO
Monitoring of supply voltage 1L+
Monitoring of supply voltage 2L+
Existing connection to network
Digital output
Fault at digital output
Diagnostic information can be read
Failure of 1L+ and 2L+
Short-circuit
Wire break
Nominal value
For "1" signal
For "1" signal
For "0" signal (residual current)
To increase performance
For redundant control of a load
With resistive load
With inductive load
With lamp load
Response threshold
I/O device digital inputs/outputs
9.2 I/O device digital outputs
Yes
Yes
Red/yellow "SF/MT" LED
Red "BF" LED
Green "ON" LED
Green "DC24V" LED
Green "P1 LK" and "P2 LK" LED; LED for
PROFINET IO infeed and loop-through
Green LED
Red LED
Yes
Yes
Yes, per channel
Yes, in the off state, per channel
Max. 30 m
Max. 30 m
24 V DC
Min. 1L+/2L+ (- 0.8 V)
2.0 A
Max. 1.5 mA
12 Ω to 3.3 kΩ
Max. 10 W
No
Supported
Yes
Max. 100 Hz
Max. 0.5 Hz
Max. 1 Hz
Typ. 1L+/2L+ (- 47 V)
Yes, electronic
Typ. 2,8 A (per channel)
123

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents