Danfoss ECL Comfort 210 Operating Manual page 99

Application a237/a337
Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A237/A337
MENU > Settings > Tank temperature
Stop difference
One DHW tank temperature sensor:
Set the number of degrees above or below the desired DHW temperature
that will stop the DHW heating / charging.
Two DHW tank temperature sensors:
Set the number of degrees below the desired DHW temperature, but
measured by the lower tank temperature sensor that will stop the DHW
heating / charging.
NOTE: If condition for stop, related to the lower DHW tank temperature
sensor, is present, the stop is done when the upper DHW tank temperature
sensor has a temperature 2 K higher than the start difference level.
See Appendix "Parameter ID overview"
Value:
Set the number of degrees.
VI.LG.R3.02
One DHW tank temperature sensor (example with positive 'Stop
difference' value):
1x194
=
X
Time
# 1 # =
Stop difference (ID 1x194)
# 2 # =
Desired DHW temperature
# 3 # =
Actual DHW temperature
# 4 # =
DHW heating / charging activity
One DHW tank temperature sensor (example with negative 'Stop
difference' value):
=
X
Time
# 1 # =
Stop difference (ID 1x194)
# 2 # =
Desired DHW temperature
# 3 # =
Actual DHW temperature
# 4 # =
DHW heating / charging activity
© Danfoss | 2017.05 | 99